Table 89 Related Parameters

<0034>

P2-02



060B

Sleep Level
Sleep Level

Sleep activates when selected level (P2-01) reaches programmed
sleep level for time specified in P2-03. The level type is determined
by P2-01. This function is only active during running while operating
in auto mode.
If P1-01 = 3, the function is active when there is only one drive
running on the network.

<0034>

Display Units for Sleep Level P2-02 when P2-01 is programmed for
the following:
P2-01=0: Display based on “Hz”
P2-01=1: Display based on “A”
P2-01=2: Display based on P1-02 Selection
P2-01=3: Display based on “rpm”

<0034>

P2-01=4: Display based on P6-02 Selection

<0034>

Note:

When P2-01 is set for a value of 2, display units will be

dependent on P1-02 setting. If P2-02 = 0, pump will sleep at
minimum speed.

0.0 ~

6000.0

0.0

Programming

P2-03



060C

Sleep Delay Time
Sleep Delay Time

Delay time before drive enters sleep mode when criteria is met as
defined by parameter P2-02.

0 ~ 3600

5 s

Programming

P2-20



0123

Alternative Sleep Activate Level
SLP Act. Level

When P2-01 Sleep Level Type is set for 0 (Output Frequency) or 3
(Output Speed), the sleep function becomes active when the output
frequency is greater or equal to the level in P2-20. When
programmed to 0, the sleep function will become active above the
P2-02 Sleep Level.

Display Units for Sleep Activate Level P2-20 when P2-01 is
programmed for the following:

<0034>

P2-01=0: Display based on “Hz”
P2-01=1: Display based on “Hz”
P2-01=2: Display based on “Hz”
P2-01=3: Display based on “rpm”
P2-01=4: Display based on “Hz”

A value of 0 disables this function.

0.0 ~

6000.0

0.0

Programming



Denotes that parameter can be changed when the drive is running.

Parameter

No.

Addr.

Hex

Parameter Name

Digital Operator Display

Description

Setting

Range

Factory

Setting

Menu

Location

P6-01

840

Flow Meter Scaling
Flow Meter Scale

Sets the scaling for the flow meter connected to terminal A1. Enter
the gal / min when the flow meter is at it's rated output. A setting of
0.0 disables all flow meter functions.

0.0 ~

6000.0

Gpm

0.0 Gpm Programming

P6-02

841

Water Flow Units
Water Flow Units

Sets the units displayed for monitor U1-95. Also sets units for
parameters P2-02 and P6-04.

0: U.S. Gallons / min (GPM)
1: U.S. Gallons / hr (GPH)
2: U.S. Barrels / min (BPM)
3: U.S. Barrels / hr (BPH)
4: U.S. Barrels / day (BPD)

0 ~ 4

0

Programming

P6-03



842

Flow Accumulation Reset
Flow Accum Reset

Resets the accumulated flow and returns the monitors U1-96 and
U1-97 to zero.

0: No Reset
7770: Reset Accum.All other settings will have no effect
NOTE:

After this parameter is changed it will automatically return to

a “0”.

0 ~ 65535

0

Programming

P6-04



843

Low Flow Level
Low Flow Level

If the drive is running, and the flow goes below this level for more
than the P6-05 time, a Low Flow fault or alarm will occur. A setting
of 0 disables the low flow detection.

0.0 ~

6000.0

(*n1)

0.0

Programming

P6-05



844

Low Flow Detection Delay Time
When Already Running
Low Flow Tim Run

Sets the amount of time the flow rate must be below the P6-04 level
before a Low Flow condition is detected

0.0 ~

6000.0 s

10

Programming

P6-06



845

Low Flow Detection Wait Time
At Start
Low Flow Time St

Sets the time the drive will wait after coming out of a zero speed
condition before activating Low Flow detection.

0.0 ~

3600.0 min

0.0

Programming