YASKAWA TM.iQp.07 iQpump Controller Programming Manual

277

o1-07

0518

Second Line User
Monitor Selection
2nd Monitor Sel

Sets the “U1” monitor always displayed on the 4th line of the digital
operator display. Effective only when o1-06 = 1.

1 ~ 94

2

Programming

134

o1-08

0519

Third Line User Monitor
Selection
3rd Monitor Sel

Sets the “U1” monitor always displayed on the 5th line of the digital
operator display. Effective only when o1-06 = 1.

1 ~ 94

91

Programming

134

Key Selections

o2-01

0505

Local / Remote Key
Function Selection
Local/Remote Key

Has no function when HOA operator is connected.
0: Disabled
1: Enabled

0 ~ 1

1

Programming

135

o2-02 0506

OFF Key Function
During Auto Run
Oper OFF Key

Determines if the off key on the digital operator will stop the drive
when drive is operating from external terminals or serial
communications.
0: Disabled
1: Enabled

0 ~ 1

1

Programming

135

o2-03

0507

User Parameter Default
Value
User Defaults

Allows storing of current parameter values as a User Initialization
Selection at parameter A1-03.
0: No Change (No user parameter set active).
1: Set Defaults (Saves current parameter settings as user initialization.
A1-03 now allows selecting <1110> for user initialization.
2: Clear All (Clears the currently saved user initialization. A1-03 no
longer allows selecting <1110>.

0 ~ 2

0

Programming

135

o2-04

0508

Drive / kVA Selection
Inverter Model #

Sets the kVA of the drive. Enter the number based on drive model #.
Use the ………… portion of the CIMR-P7…………-107 Model
Number.

0 ~ FF

kVA

Dependent

Programming

135

o2-05

0509

Frequency Reference
Setting
Method Selection
Operator M.O.P.

Determines if the Data / Enter key must be used to input a frequency
reference from the digital operator.
0: Disabled - Data / Enter key must be pressed to enter a frequency
reference.
1: Enabled: -Data / Enter key is not required. The frequency reference
is adjusted by the up and down arrow keys on the digital operator
without having to press the data / enter key.

0 ~ 1

0

Programming

136

o2-06

050A

Operation Selection
when Digital Operator is
Disconnected
Oper Detection

Determines if the drive will stop when the digital operator is removed.
0: Disabled - The drive will not stop when the digital operator is
removed.
1: Enabled - The drive will fault (OPR) and coast to stop when the
operator is removed.

0 ~ 1

1

Programming

137

o2-07

050B

Cumulative Operation
Time Setting
Elapsed Time Set

Sets the initial value of the elapsed operation timer.

0 ~

65535 hr

0 hr

Programming

137

o2-08

050C

Cumulative Operation
Time Selection
Elapsed Time Run

Sets how time is accumulated for the elapsed timer (o2-07).
0: Power-On Time (Time accumulates whenever drive is powered).
1: Running Time (Time accumulates only when drive is running)

0 ~ 1

1

Programming

137

o2-10

050E

Cumulative Cooling Fan
Operation Time Setting
Fan ON Time Se

t

Sets the initial value of the heatsink fan operation time.

0 ~

65535 hr

0 hr

Programming

137

o2-12

0510

Fault Trace / Fault
History Clear Function
FLT Trace Ini

t

Clears the fault memory contained in the U2 and U3 monitors.
0: Disabled (no effect).
1: Enabled - resets U2 and U3 monitors, and returns o2-12 to zero.

0 ~ 1

0

Programming

138

o2-14

0512

kWh User Monitor (U1-
29) Initialization
kWh MonitorClear

Used to reset the kilowatt Hour monitor to zero
0: Disabled (no change)
1: Clear all - Resets U1-29 to zero and returns o2-14 to zero.

0 ~ 1

0

Programming

138

Copy Function

o3-01

0515

Copy Function Selection
Copy Function Sel

This parameter controls the copying of parameters to and from the
digital operator.
0: COPY SELECT (no function)
1: INV -> OP READ - All parameters are copied from the drive to the
digital operator.
2: OP -> INV WRITE - All parameters are copied from the digital
operator into the drive.
3: OP <--> INV VERIFY - Parameter settings in the drive are
compared to those in the digital operator.
Note:

When using the copy function, the drive model number and

software number (U1-14) must match or an error will occur.

0 ~ 3

0

Programming

139

Parameter

No.

Addr.

Hex

Parameter Name

Digital Operator

Display

Description

Setting

Range

Factory

Setting

Menu

Location

Page

No.