YASKAWA TM.iQp.07 iQpump Controller Programming Manual

H2-02

(continued)

040C

Terminal M3-M4
Function Selection
Term M3-M4 Sel

42: Pump Fault
Function Active in hand, auto, pre-charge and thrust mode
Open: No Dedicated Pump Faults are active.
Closed: Dedicated pump fault active (Low Feedback Fault, High
Feedback Fault, Over Cycling Fault, Pump Protection Fault,
Thermostat Fault, Low Water Fault, Ext. Pump Fault).
43: Mot 2 Alternate

<0034>

Used in conjunction with the 2-motor alternation function.
Open: Motor 1 in use (or 2-motor alternation is disabled).
Closed: Motor 2 in use.
44: Sleep Active

<0034>

Closed: Drive is in the sleep mode.
45: Start Lvl Delay

<0034>

Closed: During the Start Level Delay Time (P1-05). Feedback has
dropped below the P1-04 level and the drive is delaying running.
46: Thrust Bearing

<0034>

Closed: The Thrust Bearing feature is active (output frequency is
between zero and P4-05).
47: Pre-charge

<0034>

Closed: The Pre-charge feature is active (configured by P4-01 ~
P4-03). -OR-
Closed: The Pre-charge 2 feature is active (configured by P4-12 ~
P4-13).
48: High Feedback

<0034>

Closed: During a “High FB / Water” Fault. -OR-
Closed: During a “Low Feedback” Alarm.
49: Low Feedback

<0034>

Closed: During a “High FB / Water” Fault. -OR-
Closed: During a “Low Feedback” Alarm.
4A: Transducer Loss

<0034>

Closed: Feedback Loss has been detected (configured by b5-12 ~
b5-14). -OR-
Closed: Feedback Loss has been detected on A1 (dual-zone PI). -OR-
Closed: During a “FBL - Feedback Loss Fault”.
4B: Set-point Not Met

<0034>

Closed: During an “NMS - Set-point Not Met” Fault. -OR-
Closed: Feedback level is outside of the P1-11 window. (P1-12 time
delay is not applied).
Note:

If P1-11 is set to zero, this digital output will always be open.

4C: Loss of Prime

<0034>

Closed: During a “LOP - Loss Of Prime” Fault. -OR-
Closed: Output current is below the P1-14 level.
Note

: If P1-14 is set to zero, this digital output will always be open.

4D: Thermostat Fault

<0034>

Closed: Thermostat Fault is present.
4E: Low Flow

<0034>

Closed: During the “Low Flow Fault” condition. -OR-
Closed: During a low flow condition as set by P6-04 ~ P6-06 (includes
“Low Flow Alarm”).
4F: Accum Level

<0034>

Closed: Accumulated level has exceeded the P6-09 and P6-10 setting.
-OR-
Closed: During the “Accum Level” Fault.
50: Utility Delay

<0034>

Closed: Drive is stopped and is waiting for the utility delay timer to
expire (configured by P4-11).
51: Run / Stop-Stop

<0034>

Closed: Drive is stopped due to the run / stop control (P4-18 and
P4-19) -OR-
Closed: Drive is stopped because the number of run / stop cycles has
completed. (P4-20)
52: Run / Stop - Finish

<0034>

Closed: Drive is stopped because the number of run / stop cycles has
completed. (P4-20)
53: Anti-Jam / De-Scale

<0034>

Closed: When the Anti-Jam or the De-Scale features are active
(configured by P7-XX).
54: During Run 2

<0034>

Closed: Whenever the drive is outputting voltage to the motor (not
base-blocked).

0 ~ 57

41

Programming

76

Parameter

No.

Addr.

Hex

Parameter Name

Digital Operator

Display

Description

Setting

Range

Factory

Setting

Menu

Location

Page