YASKAWA TM.iQp.07 iQpump Controller Programming Manual

285

P4-08

<0032>

011C

Protection Fault Auto
Restart Enable
Prot Flt Restrt

Setting to enable / disable Auto Restart for the following iQpump
protection faults (N = disable / Y = enable):
SP: Not Maintaining SetPoint (P1-11)
LOP: Loss of Prime (P1-16)
POC: Pump Over Cycling (P2-08))
0: POC = N LOP = N SP = N
1: POC = N LOP = N SP = Y
2: POC = N LOP = Y SP = N
3: POC = N LOP = Y SP = Y
4: POC = Y LOP = N SP = N
5: POC = Y LOP = N SP = Y
6: POC = Y LOP = Y SP = N
7: POC = Y LOP = Y SP = Y

Note:

Parameter L5-01 needs to be set to “1” and program L5-03 needs

to be set to the applicable time.

0 ~ 7

0

Programming

194

P4-09

<0032>

011D

Loss of Prime Maximum
Restart Time After Fault
LOP Max Rstrt T

If the restart fails (or is not attempted due to a continuing fault
condition) the drive waits this many minutes before attempting another
restart.

Note:

This parameter will take the place of L5-03 during a Loss of

Prime Fault restart attempt.

0.2 ~

6000.0 min

0.2 min Programming

194

P4-10



011E

Auto Mode Operator Run
Power Down Storage.
AMO PwDn-Storage

Stores the run status in the Auto mode when operating from digital
operator (b1-02 = 0).
0: Disabled.
1: Enabled.

0 ~ 1

0

Pump Quick

Setup

199

When the drive is powered down while running, then upon power-up it will
automatically initiate an internal run command.

P4-11



<0034>

82A

Utility Start Delay
Utility Delay

Sets the amount of time the drive will delay starting if a run command
is present at power up.
A setting of 0.0 disables this function.
If P1-01 = 3, the drive is unavailable to the network (Pump Off
Network) when the function is active.

<0034>

0.0 ~

1000.0 min 0.2 min Programming

P4-12



<0034>

82B

Pre-charge Frequency 2
Pre-charge Freq2

Frequency reference used when Pre-charge 2 function is active.
A value of 0.00 disables this function.

0.00 ~

120.00 Hz

0.00 Hz Programming

P4-13



<0034>

82C

Pre-charge Time 2
Pre-charge Time2

Time at which the drive will spend at the Pre-charge Frequency 2
(P4-12) speed during pre-charge.
A value of 0.0 disables this function.

0 ~

3600.0 min 0.0 min Programming

P4-14

<0034>

82D

Two Motor Alternation
Selection
Mot 2 Alternate

Selects if the alternation feature is enabled.
0: Disabled
1: Enabled
2: Motor 1 Only
3: Motor 2 Only

0 ~ 3

0

Programming

P4-15

<0034>

82E

Alternation Operation
Selection
Alternation Oper

Selects the drive behavior when the internal alternation timer expires.
0: Wait For Stop
1: Immediate

0 ~ 1

0

Programming

P4-16

<0034>

82F

Alternation Time
Alternation Time

Selects the amount of time each motor will run before the drive
switches to the other motor.

1.0 ~

100.0 hr

24.0 hr

Programming

P4-17

<0034>

830

Dual Zone PID Feedback
Bandwidth Range
Dual Zone Range

Determines the detection bandwidth for the dual zone PI control.

0 ~ 6000.0

(system

units

P1-02)

10.0

(system

units

P1-02)

Programming

P4-18



<0034>

831

Run-Stop Control Run
Time
R-S Run Time

This parameter sets the amount of time the drive will run for when the
run-stop control is enabled. It will also set the “timed” run time when
enabled (b1-02 = 5).

0.0 ~

6000.0 min 0.0 min Programming

P4-19



<0034>

832

Run-Stop Control Stop
Time
R-S Stop Time

This parameter sets the amount of time the drive will stop for when the
run-stop control is enabled.

0.0 ~

6000.0 min 0.0 min Programming

P4-20



<0034>

833

Run-Stop Control Cycles
R-S Cycle Count

This parameter determines how many run-stop cycles the drive will
execute before staying stopped.

0 ~ 1000

0

Programming

