YASKAWA TM.iQp.07 iQpump Controller Programming Manual

69

Function: High Water Level (Setting: 76)

<0034>

Function will be active whenever the drive is running. Function logic depends on parameter P1-15 (Water DI Config).

P1-15 = 0 or 1 (Normally Open)
Closed: High Water Level Fault
Open: Reservoir / Tank is filled to normal level

P1-15 = 2 or 3 (Normally Closed)
Closed: Reservoir / Tank is filled to normal level.
Open: High Water Level Fault

Function: Hand Mode (Setting: 80)

A digital input can be configured to operate the drive in the hand mode from an external contact as a Hand Mode command (H1-0x = 80).

In conjunction with the digital input programmed to hand mode, the run command source has to be programmed to 1 (b1-02 = 1:
Terminals).

The multi-function digital input terminal S6 is programmed for Hand Mode as a factory default (H1-04 = 80).

Figure 1.49

Figure 49. Connection Diagram for External Hand Mode Contact (b1-02 = 1)

Function: Disable Sleep Mode (Setting: 81)

A digital input can be configured to enable or disable the Sleep Mode (H1-0x = 81). The Sleep Mode is only active when the drive is in
the Auto Mode. A contact closure into the multi-function digital input will disable the Sleep Mode. Also, the Feedback Drop Detection
and Over Cycle Protection will also be disabled. When the digital input is open, the Sleep Mode, Feedback Drop Detection and Over
Cycle Protection will be enabled.

Figure 1.50

Figure 50. Wiring Diagram

b1-02 = 1