YASKAWA TM.iQp.07 iQpump Controller Programming Manual

P7-08



<0034>

856

De-Scale Acceleration
Time
De-Scale Accel

Sets the amount of time it will take the drive to accelerate from zero to
the De-Scale frequency reference P7-05 (internally limited 0.1 ~
6000.0 s).

0.0 ~

600.0 s

2.0 s

Programming

P7-09



<0034>

857

De-Scale Deceleration
Time
De-Scale Decel

Sets the amount of time it will take the drive to decelerate from the
De-Scale frequency reference P7-05 to zero (internally limited 0.1 ~
6000.0 s).

0.0 ~

600.0 s

2.0 s

Programming

P7-10



<0034>

858

De-Scale Pump Run
Time
De-Scale Time

Sets the number of pump operating hours (pump speed > 0) before a
De-Scale routine will run.

1.0 ~

2000.0 hr

168.0 hr Programming

P7-11



<0034>

859

Anti-Jam Release Time
Anti-Jam Release

Sets the amount of time that the current must be below the P7-03 level
in order to resume normal operation.

0.5 ~

10.0 s

2.0 s

Programming

Pressure and Level Control

P8-01

<0034>

860

Pressure and Level
Control Select
Pres&Lvl Control

Enables / Disables the Constant Pressure With Well Draw Down
Control.
0: Disabled
1: Enabled

0 ~ 1

0

Programming

P8-02

<0034>

861

Water Level Scaling
Water Lvl Scale

Sets the full scale (20 mA) output of the pressure transducer that is
connected to Terminal A1.

5 ~

500 psi

100 psi Programming

P8-03



<0034>

862

Water Level Set-point
Water Lvl Setpnt

Sets the amount of water above the sensor that the drive will attempt to
regulate to.

0.0 ~

1200.0 ft

20.0 ft

Programming

P8-04



<0034>

863

Minimum Water Level
Min Water Level

When the amount of water above the sensor drops below this level for
more than the P2-03 time, the drive will go to sleep.

10.0 ft

Programming

P8-05



<0034>

864

Wake-Up Water Level
Wake-Up Level

If the drive has been forced to sleep based upon the minimum water
level (P8-04), the water will have to go above this level for more than
the P1-05 time in order to wake up.

30.0 ft

Programming

P8-06



<0034>

865

Level Control Minimum
Speed
Level Min Spd

This parameter sets the minimum speed the drive will be allowed to run
at when the drive is controlling the water level. When the drive is
controlling pressure or this parameter is set less than P1-06 and P4-05,
P1-06 and P4-05 will be used as the minimum speed.

0.00 ~

120.00 Hz

0.00 Hz Programming

P8-07



<0034>

866

Low Level Detection
Level
Low Level Detection

When the amount of water above the sensor drops below the level for
more than the P8-08 time, the drive will respond depending on the
P8-09 setting.
A setting of 0.0 disables this detection.

0.0 ~

1200.0 ft

0.0 ft

Programming

P8-08



<0034>

867

Low Level Detection
Time Delay
Low Lvl Det Tm

Sets the amount of time delay that the water level must drop below the
P8-07 level before the drive will react.

0.0 ~

300.0 min

0.1 min Programming

P8-09

<0034>

868

Low Level Behavior
Low Lvl Behavior

Sets how the drive will respond when the water level in the well drops
below the P8-07 level for more than the P8-08 time.
0: No Display (Digital Output Only)
1: Alarm Only
2: Fault

0 ~ 2

1

Programming

P8-10



<0034>

869

Level Control
Proportional Gain
Lvl Ctrl P Gain

Sets the proportional gain for the water level control.

0.00 ~

25.00

2.00

Programming

P8-11



<0034>

86A

Level Control Integral
Time
Lvl Ctrl I Time

Sets the integral time for the water level control. A setting of zero
disables the water level control integrator.

0.0 ~

360.0 s

5.0 s

Programming

Network Options

P9-01

<0034>

0880

Lead Drive Selection
Lead Drive Sel

Specifies how the next Lead Drive is selected.
0: Next Available
1: Lowest Runtime

0 ~ 1

1

Programming

P9-02

<0034>

0881

Feedback Source
Feedback Source

Defines which signal to use for PI Feedback when P1-01 = 3.
0: Analog Only
1: Ana->Net, No Alarm.
2: Ana->Net, Alarm
3: Network Only
Setting has no effect when P1-01 = 3.

0 ~ 3

0

Programming

P9-03



<0034>

0882

Alternation Time
Alternation Time

Specifies the time for a drive to request alternation, influenced by the
Alternation Mode P9-04.
The alternation feature is disabled when this parameter is set to 0.

0 ~ 1000 hr

24 hr

Programming

