290

YASKAWA TM.iQp.07 iQpump Controller Programming Manual

P9-17



<0034>

0890

Setpoint Modifier
Set-pt Modifier

System Set-point is incremented with this value depending on the
number of pumps running.
Pump 1: Set-point
Pump X: Set-point + {(X-1) (P9-17)}

-6000.0 ~

6000.0

(system

units

P1-02)

0.0

(system

units

P1-02)

Programming

P9-18



<0034>

0891

High Feedback Quick
De-Stage
High FB De-stage

Determines the feedback level to trigger a quick de-stage, set as a
percentage of parameter P1-09. The quick de-stage ignores parameters
P9-12 to P9-15 and only uses an internal 2 second delay.

0.0 ~

100.0 %

90.0 %

Programming

P9-19



0892

Alternation Unit
Alternation Unit

Selects the unit for P9-03

0: Hours (hr)
1: Minutes (min)

0 ~ 1

0

Programming

P9-20

0893

Allow Network Run
Allow Net Run

Specifies when a network run command is allowed:
0: Always
1: First / Alternation
2: First Only
3: Alternation Only

0 ~ 3

0

Programming

P9-21



0894

Run Priority
Run Priority

Sets the Lead Drive selection priority overriding the P9-01 selection. If
multiple drives have the lowest P9-21 value, then P9-01 determines
which drive becomes the Lead.

1 ~ 16

8

Programming

P9-22



<0034>

0895

System Fault Retry
System Flt Retry

Determines the number of times the iQpump Memobus Network will
allow automatic restarts of system faults. The drive uses parameter
L5-03 in determining when to attempt a system fault restart.
For proper operation, this parameter should be set the same for all
network drives.

0 ~ 10

5

Programming

P9-23



<0034>

0896

Max Number of Running
Pumps
MaxPumps Running

Limits the maximum number of pumps that can run on the system.

1 ~ 16

16

Programming

P9-24



<0034>

0897

Lead Swap @ Sleep
Lead Swap @ Sleep

When the Lead DRive has been in Sleep for this amount of time and
there is another drive available with a lower P9-21, then this drive will
request for a swap.
A setting of 0 disables this function.

0 ~ 7200 s

0 s

Programming

P9-25

<0034>

0898

Highest Node Address
Highest Node Adr

Defines the highest possible node address in the Memobus network. To
yield optimal network performance, it is recommended to set the serial
communication address H5-01 starting from 01h and then
consecutively up to the last drive and then setting this parameter to that
H5-01 address.

02 h ~ 10 h

08 h

Programming

P9-26

<0034>

0899

Master Time-Out
Master Time-0ut

Sets the minimum amount of time that the slave drives will wait for a
message from the master before performing the action set in P9-27.

3.0 ~

10.0 s

4.0 s

Programming

P9-27

<0034>

089A

Network Recovery
Network Recovery

When no messages are received from the master for the time set in
P9-26, the slave drive will act according to this setting:
0: Automatic - drive will attempt to assume master functionality.
1: Slave / Resume - drive will continue running when the master is lost
and will wait for a master to come on-line.
2: Slave / Stop - drive will stop running when the master is lost and will
wait for a master to come on-line.
3: Fault MSL - fault the drive with an MSL (Master Lost).

0 ~ 3

0

Programming

P9-28

<0034>

089B

NETSCAN Alarm Time
NETSCAN Alrm Time

Sets the amount of time that the slave drives will wait for a message
from the master before displaying a NETSCAN alarm.

1.0 ~

10.0 s

2.0 s

Programming

P9-29



<0034>

089C

Net Start Delay
Net Start Delay

After the first drive on the network has been put on Auto mode, the
network will wait this amount of time before selecting and starting the
Lead Drive.

0.0 ~

60.0 s

2.0 s

Programming

Auto-Tuning

T1-02

0702

Motor Rated Power
Mtr Rated Power

Sets the motor rated power in kW.
Note:

T1-02 should be left at the default value (last 3 digits of the drive

model number).

0.00 ~

650.0

kVA

Dependent

Auto-Tuning

258

T1-04

0704

Motor Rated Current
Rated Current

Sets the motor rated current. (Used only during an auto-tune.)

kVA

Dependent

kVA

Dependent Auto-Tuning

258



Denotes that parameter can be changed when the drive is running.

Parameter

No.

Addr.

Hex

Parameter Name

Digital Operator

Display

Description

Setting

Range

Factory

Setting

Menu

Location

Page

No.