H5-09 Communication Error Detection Time
Setting Range:
0.0 ~ 10.0 s
Factory Default: 2.0 s
The setting of parameter H5-09 determines the length of time that serial communications must be lost before a CE fault occurs. Setting
H5-09 = 0 will configure the iQpump drive for the quickest CE fault detection but may cause nuisance faults. The iQpump drive power
should be cycled after a change is made to this parameter.