Yaskawa iQpump Controller Programming Manual User Manual

Page 230

Advertising
background image

230

YASKAWA

TM.iQp.07 iQpump Controller Programming Manual

Table 103 Function Text

Table 104 Monitors

Table 105 Multi-Function Input Setting

Table 106 Multi-Function Output Setting

Table 107 Faults

Table 108 Alarms

Function Number

Function Name

Digital Operator Display

P6

Flow Meter Setup

Flow Meter Setup

P8

Pressure and Level Control

Pres&Lvl Control

Monitor

No.

Addr.

Hex

Monitor Name

Digital Operator Display

Description

U1-95

725

Flow Rate
Flow Rate

Displays the flow rate, based upon the voltage present on Terminal A1 and parameters P6-01 and P6-02. A
two second 1st order filter will be applied to this monitor.

U1-96

72A

Volume Accumulated (Fine)
Volume (Fine)

Displays the volume that has been measured by terminal A1. Total volume can be calculated as follows:
Total Volume = U1-97 * 1000 + U1-96.

Value retained in EEPROM.

U1-97

72B

Volume Accumulated (Course)
Volume (Course)

Displays the volume that has been measured by terminal A1. Total volume can be calculated as follows:
Total Volume = U1-97 * 1000 + U1-96.

Value retained in EEPROM.

U1-98

72C

Water Level
Water Level

Displays the amount of water above the water level sensor.

Setting

Description

75

Reset Accum
Closed: Volume accumulated will be reset to zero (and held at zero if digital input remains closed).

Setting

Description

57

Low Water Level
This will energize if the level in the well drops below the Low Level Detection Level (P8-07) for more than the Low Level Detection Delay
Time (P8-08), or if there is a LOWWL - Low Water Level Fault.

Fault Display

Description

Cause

Countermeasures

LOWFL

Low Flow

Low flow has been detected by the flow
meter.

Not enough flow, or incorrect “P6” settings

LOWWL

Low Water Level

Low Water Level

Water Level has gone below the P8-07 level for more than the P8-
08 time.

ACCUM

Accum Level

Accumulated Level

Accumulated level has exceeded the P6-09 and P6-10 settings.

Reset the accumulated level
(P6-03 or via digital input)

OPE13

Terminal A1

Programming error

Terminal A1 is being assigned to more than one of the following
functions.

- Frequency Reference (b1-01 = 1)
- Dual Zone PI is enabled (b5-01 = 2)
- Flow Meter Enabled (P6-01 > 0)
- Level Control Enabled (P8-01 =1)
- Hand Mode Ref Term A1 (P5-01 = 0)

Reprogram b1-01, b5-01, P6-01
or P8-01.

OPE14

FlowMtrNotEnable

Programming error

The sleep level type has been set to “FlowMtr-Term A1”
(P2-01 = 4) but the flow meter function is not enabled
(P6-01 = 0.0)

Reprogram P2-01 or P6-01.

HIFLO

High Flow

High flow has been detected by the flow
meter.

Too much flow or incorrect “P6” settings.

Alarm Display

Description

Cause

Countermeasures

LOWFL

Low Flow

Low flow has been detected by the flow
meter.

Not enough flow, or incorrect “P6” settings

LOWWL

Low Water Level

Water Level has gone below P8-07 level
for more than the P8-08 time.

ACCUM

Accum Level

Accumulated Level

Accumulated level has exceeded the P6-09 and P6-10 settings.

Reset the accumulated level
(P6-03 or via digital input)

Advertising