YASKAWA TM.iQp.07 iQpump Controller Programming Manual

253

Table 120 Monitors

<0034>

P9-07



0886

Lag Fixed Speed Delay
Lag Fix Spd Dly

When the drive changes from a lead to a lag and P9-05 = 0, this time
specifies how long before the drive runs at the P9-06 speed.

0 ~

1000 s

5 s

Programming

P9-08

0887

Add Pump Mode
Add Pump Mode

Selects the detection method for staging a new pump.
0: Output Frequency
1: Feedback
2: Feedback + Fout

0 ~ 2

0

Programming

P9-09



0888

Add Freq Level
Add Freq Lvl

When P9-08 = 0 and the output frequency rises above this level for
the time set in P9-11, the lead drive will request for a new lead drive
through the iQpump MEMOBUS / Modbus network.

When P9-08 = 2 and the output frequency rises above this level and
the delta feedback (setpoint - feedback) has exceeded the level set in
P9-10 for the time set in P9-11, the lead drive will request for a new
lead drive through the iQpump MEMOBUS / Modbus network.

0.0 ~

120.0 Hz

56.0 Hz Programming

P9-10



0889

Add Delta Level
Add Delta Lvl

Sets the amount of time it will take the drive to accelerate from zero
to the De-Scale frequency reference P7-05.
(Internally limited 0.1 ~ 6000.0 s)

0 ~ 6000.0

(system

units

P1-02)

5.0

(system

units

P1-02)

Programming

P9-11



088A

Add Delay Time
Add Dly Time

Delay time before a new lead drive is added to the system.

0.~ 3600 s

10 s

Programming

P9-12

088B

Remove Pump Mode
Remove Pump Mode

Selects the detection method for de-staging to the previous lead
pump:
0: Output Frequency
1: Feedback
2: Feedback + Fout

0 ~ 2

0

Programming

P9-13



088C

Remove Freq Level
Remove Freq Lvl

When P9-12 = 0 and the output frequency is below this level for the
time set in P9-15, the lead drive will request to be removed from the
system through the iQpump MEMOBUS / Modbus network.

When P9-12 = 2 and the output frequency drops below this level and
the delta feedback (feedback - setpoint) has exceeded the level set in
P9-14 for the time set in P9-15, the lead drive will request to be
removed from the system through the iQpump MEMOBUS / Modbus
network.

0.0 ~

120.0 Hz

40.0 Hz Programming

P9-14



088D

Remove Delta Level
Remove Delta Lvl

When P9-12 = 1 and the delta feedback (feedback - setpoint) has
exceeded this level for the time set in P9-15, the lead drive will
request to be removed from the system through the iQpump
MEMOBUS / Modbus network.

When P9-12 = 2 and the delta feedback has exceeded this level and
the output frequency is below P9-13 for the time set in P9-15, the
lead drive will request to be removed from the system through the
iQpump MEMOBUS / Modbus network.

0 ~ 6000.0

(system

units

P1-02)

0.0

(system

units

P1-02)

Programming

P9-15



088E

Remove Delay Time
Remove Dly Time

Delay time before the lead drive is removed from the system.

0.~

3600 sec

10 s

Programming

P9-16



088F

Stabilization Time
Stabilize Time

Time used to stabilize the system when a pump is staged or de-
staged. Lead-lag control and pump protection is suspended during
this time.

0.~

3600 sec

3 s

Programming

P9-17



0890

Setpoint Modifier
Set-Pt Modifier

System Setpoint is incremented with this value depending on the
number of pumps running.
Pump 1: Setpoint
Pump X: Setpoint + ((X-1) (P9-17))

-6000.0 ~

6000.0

(system

units

P1-02)

0.0

(system

units

P1-02)

Programming

P9-18



0891

High Feedback Quick De-stage
High FB De-stage

Determines the feedback level to trigger a quick de-stage, set as a
percentage of parameter P1-09. The quick de-stage ignores
parameters P9-12 to P9-15 and only uses an internal 2 s delay. A
setting of 0 disables the High FB De-stage feature.

0.0 ~

100.0%

90.0%

Programming

P9-23



0896

Max Number of Running Pumps
MaxPumps Running

Limits the maximum number of pumps that can run on the system.

1 ~ 16

16

Programming

P9-29



089C

Net Start Delay
Net Start Delay

After the first drive on the network has been put on Auto mode, the
network will wait this amount of time before selecting and starting
the Lead Drive.

0.0 ~

60.0 s

2.0 s

Programming



Denotes that parameter can be changed when the drive is running.

Monitor

No.

Addr.

Hex

Monitor Name

Digital Operator Display

Description

U1-62

007D

Running Queue No
Running Queue No

Position in the iQpump MEMOBUS / Modbus Multiplex Running Queue

Parameter

No.

Addr.

Hex

Parameter Name

Digital Operator Display

Description

Range

Default

Menu

Location