YASKAWA TM.iQp.07 iQpump Controller Programming Manual

173

Figure 1.125

Figure 129.

Auxiliary Pump De-Staging (OFF)

The de-staging of the auxiliary pumps 2 and 3 will occur in the reverse order of the staging process described previously.

The de-staging of auxiliary pump 3 occurs when the output frequency falls below the Pump 3 Frequency Shutdown Level (P3-10) for the
time programmed in the Shutdown Pump Delay Time (P3-06).

The de-staging of pump 2 occurs when the auxiliary pump 3 is de-staged and the output frequency falls below the Pump 2 Frequency
Shutdown Level (P3-09) for the time programmed in the Shutdown Pump Delay Time (P3-06). Refer to

Figure 130.

for the de-staging of

the auxiliary pumps 2 and 3 using the “output frequency” control method.

TIME

Output Frequency

Add Pump Delay Time

P3-04

Feedback

Auto Mode Run

Multi-function

Output #40

Wait for Start

Max-Multi Level

P3-02

STOP, 0Hz

0%

OFF Mode

Start Level

P1-04

ADD PUMP 2

AUTO MODE RUN:

Start System, Incoming Run Command

Start System

Start Level Delay

P1-05

START DELAY

System

Set-Point

Add Pump Delay Time

P3-04

Multi-function

Output #41

ADD PUMP 3

PUMP 1

Multiplex Stabilize Time

P3-11

Multiplex Stabilize Time

P3-11