Table 72 Parameters

P4-02 Pre-charge Frequency

Setting Range:

0.00 ~ 120.00

<0034>

Factory Default: 0.00 Hz

The iQpump drive can be configured for a pre-charge function. The frequency reference used by the pre-charge function is programmed
in the Pre-charge Frequency (P4-02).

Refer to Pre-charge Level (P4-01) for more details.

The Pre-charge Frequency (P4-02) works in conjunction with the Pre-Change Level (P4-01).

P4-03 Pre-charge Time

Setting Range:

0.0 ~ 3600.0 min

Factory Default: 0.0 min

The iQpump drive can be configured for a pre-charge function. The maximum allowable time for the pre-charge function is programmed
in the Pre-charge Time (P4-03). Setting P4-03 to a value of 0 will disable the pre-charge function.

Refer to Pre-charge Level (P4-01) for more details.

The Pre-charge Time (P4-03) works in conjunction with the Pre-Change Level (P4-01).

P4-04 Thrust Bearing Acceleration Time

<0032>

Setting Range:

0.0 ~ 600.0

<0034>

Factory Default: 1.0 s

The iQpump drive can be configured for a thrust bearing function. The acceleration time, when the thrust bearing function is enabled (P4-
05 > 0), is programmed in the Thrust Bearing Acceleration Time (P4-04).

Refer to Thrust Bearing Frequency (P4-05) for more details.

The Thrust Bearing Acceleration Time (P4-04) works in conjunction with the Thrust Bearing Frequency (P4-05).

Function Description:

<0034>

Thrust Accel Modification. When the drive is started and during Thrust Bearing operation, the drive will accelerate to the Thrust
Frequency (P4-05) in the amount of time specified by the Thrust Bearing Acceleration Time Parameter (P4-04). Actual (internal)
acceleration time is calculated as follows:

Internal Accel Rate = Thrust Accel Time x (fmax / thrust frequency) = P4-04 x E1-04 / P4-05

The internal accel rate during thrust bearing operation is limited to a maximum of 600 seconds.

Parameter

No.

Addr.

Hex

Parameter Name

Digital Operator Display

Description

Range

Default

Menu

Location

P4-12



115

Pre-charge Frequency 2
Pre-charge Freq2

Frequency reference used when Pre-charge 2 function is active.

A value of 0.00 disables this function.

0.00 ~

120.00 Hz

0.00 Hz Programming

P4-13



116

Pre-charge Time 2
Pre-charge Time2

Time at which the drive will spend at the Pre-charge Frequency 2
(P4-12) speed during pre-charge.

A value of 0.0 disables this function.

0.0 ~

3600.0 min 0.0 min Programming

