TM.iQp.07 iQpump Controller Programming Manual

H4-05 Terminal AM Gain Setting

Setting Range:

0.0 ~ 1000.0%

Factory Default: 50.0%

Refer to parameter H5-05 in Appendix A for description details.

H4-06 Terminal AM Bias Setting

Setting Range:

-110.0% ~ +110.0%

Factory Default: 0.0%

Refer to parameters H4-02 and H4-03 sections for description details.

H4-07 and H4-08 Terminal Signal Level Selections

When the iQpump drive is equipped with the optional, removable terminal board with 4-20 mA outputs (p/n ETC618120), parameters
H4-07 and H4-08 determine whether analog outputs are configured as 0-10 Vdc or 4-20 mA. Refer to the documentation for the optional
terminal board as the proper jumper settings are required in addition to programming H4-07 and H4-08.

If the standard removable terminal board is being used, the settings of H4-07 and H4-08 have no effect.

Parameter No.

Setting

Description

H4-07

0

Terminal FM Signal Level Selection, 0 - 10 Vdc (

factory default

)

H4-08

1

Terminal AM Signal Level Selection, 4 - 20 mA