YASKAWA TM.iQp.07 iQpump Controller Programming Manual

183

The iQpump drive can be configured for multiplex pumping operation. A time delay can be programmed to allow the system to stabilize
when a pump is staged (turned ON) or de-staged (turned OFF). The time used for system stabilization is programmed into the Multiplex
Stabilization Time (P3-11). When a pump is staged (turned ON), the stabilization time (P3-11) temporarily disables the lead / lag
functionality during this time period to prevent pump cycling.

This function is only active when the Pump Mode (P1-01 > 0) is greater than 0.

Refer to Lead-Lag Control (P3-01) for more details.

Note: The pump protection and lead-lag control are suspended during this time period.

Figure 1.133

Figure 137.

P3-12 Delta Setpoint Feedback Acc / Dec Changeover

Setting Range:

0.0 ~ 6000.0

Factory Default: 0.0

The iQpump drive can be configured for multiplex pumping operation. The acceleration (Acc) and deceleration (Dec) times can be
changed when the difference between the delta setpoint and feedback are within the programmed level in the Delta Setpoint Feedback
Acc / Dec Changeover (P3-12).

The acceleration and deceleration times during this changeover are programmed into C1-05 and C1-06, respectively.

This function is used to improve the pump regulation.

TIME

Output Frequency

Add Pump Delay Time P3-04

Feedback

Auto Mode Run

Multi-function

Output #40

Wait for Start

Max-Multi Level

P3-02

STOP, 0Hz

0%

OFF Mode

Start Level

P1-04

ADD PUMP 2

AUTO MODE RUN:

Start System, Incoming Run Command

Start System

Start Level Delay

P1-05

START DELAY

System

Set-Point

Add Pump Delay Time

P3-04

Multi-function

Output #41

ADD PUMP 3

PUMP 1

Multiplex Stabilize Time

P3-11

Multiplex Stabilize Time

P3-11

Lead/Lag Functions

Disabled until

stabilization timer

expires