YASKAWA TM.iQp.07 iQpump Controller Programming Manual

H4-02



041E

Terminal FM Gain
Setting
Terminal FM Gain

Sets Terminal FM output voltage (in percent of 10 V) when selected
monitor is at 100 % output.

0.0 ~

1000.0 %

100.0 % Programming

95

H4-03



041F

Terminal FM Bias
Setting
Terminal FM Bias

Sets Terminal FM output voltage (in percent of 10 V) when selected
monitor is at 0 % output.

–110.0 ~

+110.0 %

0.0 %

Programming

95

H4-04

0420

Terminal AM Monitor
Selection
Terminal AM Sel

Selects which monitor will be output on Terminals AM and AC.
1: Frequency Ref (100 % = max. output frequency)
2: Output Freq (100 % = max. output frequency)
3: Output Current (100 % = drive rated current)
6: Output Voltage (100 % = 230 V or 100 % = 460 V)
7: DC Bus Voltage (100 % = 400 V or 100% = 800 V)
8: Output kWatts (100 % = drive rated power)
15: Term A1 Level
16: Term A2 Level
18: Mot SEC Current (100 % = Motor rated secondary current)
20: SFS Output (100 % = max. output frequency)
24: PI Feedback
31: Not Used
36: PI Input
37: PI Output (100 % % = max. output frequency)
38: PI Set-point
Note:

100 % = 10 V DC output x AM gain setting (H4-05).

1 ~ 38

<0032>

8

Programming

95

H4-05



0421

Terminal AM Gain
Setting
Terminal AM Gain

Sets Terminal AM output voltage (in percent of 10 V) when selected
monitor is at 100 % output.

0.0 ~

1000.0 %

50.0 %

Programming

96

H4-06



0422

Terminal AM Bias
Setting
Terminal AM Bias

Sets Terminal AM output voltage (in percent of 10 V) when selected
monitor is at 0 % output.

–110.0 ~

+110.0 %

0.0 %

Programming

96

H4-07

0423

Terminal FM Signal
Level Selection
AO Level Select1

0: 0 - 10 Vdc
2: 4 - 20 mA*

0 or 2

0

Programming

96

H4-08

0424

Terminal AM Signal
Level Selection
AO Level Select2

0: 0 - 10 Vdc
2: 4 - 20 mA*

0 or 2

0

Programming

96



Denotes that parameter can be changed when the drive is running. * An analog output of 4 - 20 mA cannot be used with the standard terminal board. Therefore an

optional terminal board (with shunt connector CN15) is needed.

Serial Communication Setup

H5-01

0425

Drive Node Address
Serial Com Adr

Selects drive station node number (address) for Terminals R+, R-, S+,
S-.
Note:

An address of “0” disables serial com.

Drive power must be cycled before the changes will take effect.
*Range is dependent on P9-25, if P1-01 = 3.

<0034>

0 ~ 20*

1F

Programming

108

H5-02

0426

Communication Speed
Selection
Serial Baud Rate

Selects the baud rate for Terminals R+, R-, S+ and S-.
0: 1200 Baud
1: 2400 Baud
2: 4800 Baud (APOGEE FLN)
3: 9600 Baud (Metasys N2)
4: 19200 Baud
Note:

Drive power must be cycled before the changes will take effect.

<0034>

0 ~ 4

3

Programming

108

H5-03

0427

Communication Parity
Selection
Serial Com Sel

Selects the communication parity for Terminals R+, R-, S+ and S-.
0: No Parity
1: Even Parity
2: Odd Parity
Note:

Drive power must be cycled before the changes will take effect.

<0034>

0 ~ 2

0

Programming

108

H5-04

0428

Stopping Method after
Communication Error
Serial Flt Sel

Selects the stopping method when a communication error is detected.
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only

0 ~ 3

3

Programming

109

H5-05

0429

Communication Error
Detection Selection
Serial Flt Dtct

Enables or disables the communications timeout detection function.
0: Disabled - A communications loss will NOT cause a
communications fault.
1: Enabled - If communications are lost for more than the time
specified in parameter H5-09, a communications fault will occur.

0 ~ 1

1

Programming

109

Parameter

No.

Addr.

Hex

Parameter Name

Digital Operator

Display

Description

Setting

Range

Factory

Setting

Menu

Location

Page

No.