L8-06 Input Phase Loss Detection Level

Setting Range:

0.0 ~ 25.0% of Drive O V Trip point

Factory Default: kVA Dependent

The iQpump drive checks for a lost input phase by monitoring the DC Bus voltage ripple. After an initial delay of approximately 12
seconds, the iQpump drive will sample the DC BUS voltage every 1.28 seconds to determine the minimum and maximum voltage
readings. The difference between the minimum and maximum voltage is averaged over ten consecutive scans. If this “averaged” value is
greater than the trip level as determined by L8-06 (L8-06 x 400 for 200 V class drives; L8-06 x 800 for 400 V class drives) the iQpump
drive shuts down and displays “PF,” an input phase loss fault.

Figure 1.104

Figure 108. Input Phase Loss Detection Diagram

L8-07 Output Phase Loss Protection

<0033>

The output phase loss detection circuit monitors the DCCT and activates when one or more of the output phases are lost. The detection
circuit calculates the RMS current value (IRMS) for each of the phases and compares it with an internal output detection level. If IRMS
decreases to or below the detection level for 10 seconds, an output phase loss (LF) fault occurs and the motor coasts to a stop.

L8-09 Output Ground Fault Detection Selection

The iQpump drive has a ground fault detection circuit that activates when the current to ground exceeds 50% of the drive’s rated output
current. The current to ground is determined by comparing the measured current on each of the output phases. If the current to ground is
determined to be above 50% of the drive’s rated output current the digital operator will display a GF and the iQpump drive will coast to
stop.

L8-10 Heatsink Cooling Fan Operation Selection

Refer to L8-11 description.

Setting

Description

0

Disabled

1

Enabled (

factory default

)

Setting

Description

0

Disabled

1

Enabled

(factory default

)

Setting

Description

0

Fan On-Run Mode (

factory default

)

1

Fan Always On

t

L8-06

Phase Loss
Fault Signal

DC Bus
Voltage

10 seconds

Fault Contact

t

Closed

Open

Input Phase Loss

Time