Important: Be aware that during rapid deceleration the iQpump drive may fault on an over voltage condition. When faulted, the iQpump
drive output shuts off allowing the motor to coast. The result is an uncontrolled motor state. Therefore, be sure to set an acceptable
deceleration time in parameter C1-09 when using the fast stop feature.

Function: Timer Function (Setting: 18)

The Timer Function works independently from the drive. For Timer operation a digital input must be configured for a Timer Function
start (H1-0x = 18), a digital output must be configured as a Timer Function output (H2-0x = 12), and the Timer Function ON-Delay and
OFF-Delay parameters (b4-01 and b4-02, respectively) must be programmed.

Once the applicable parameter are programmed the Timer Function start digital input must be closed at least as long as the setting of b4-
01 before the Timer Function output will close. The Timer Function input must be open for at least as long as the setting of b4-02 before
the Timer Function output will reopen.

Figure 1.46

Figure 46. Timer Function Time Chart

Function: Program Lockout (Setting: 1B)

A Program Lockout digital input will allow changing of parameter values when it is open but prevent changing of any iQpump drive
parameter value except the Speed Command when it is closed. Parameter values can be viewed even when a Program Lockout is active.

Function: PI Disable (Setting: 19)

When the PI Function has been enabled by b5-01 (PI Mode Selection), it can be indefinitely disabled by closing a digital input configured
as a PI Disable input (H1-0x = 19). When disabled, the iQpump drive operates as a standard drive that does not have PI enabled.

Fast Stop

N.C.

Input

Output

Frequency

RUN

H1-0x=17

ON (Closed)

OFF (Open)

OFF (Open)

ON (Closed)

C1-09

TIME

Multi-function Contact
Input: Timer Function

Multi-function Contact
Output: Timer Function

b4-01

b4-01

b4-02

ON

OFF

ON
OFF

b4-02

(CL OSED

(CLOSE

(OPEN)

(OPEN)