Time Delayed External Fault(s)

Allow all external faults to have a settable time delay.

- An “On-Delay” timer will be applied to the external fault if it is “Normally Open”.

- An “Off-Delay” timer will be applied to the external fault if it is “Normally Closed”.

- If the external fault is set to “During Run”, the time delay will start after a run command is received.

Figure 1.59

Figure 59. External Fault 3 - Normally Open, Always Detected, Coast To Stop

Figure 1.60

Figure 60. External Fault 3 - Normally Closed, Always Detected, Coast To Stop

EF3 Input

(H1-01 = 24)

External Fault 3 – Normally Open, Always Detected, Coast To Stop

H1-12

EF3 Delay Tm

H1-12

EF3 Delay Tm

H1-12

EF3 Delay Tm

H1-12

EF3 Delay Tm

Fault Reset

Input

Run

Command

Output

Frequency

Fault Output

(External Fault 3)

EF3 Input

(H1-01 = 25)

External Fault 3 – Normally Closed, Always Detected, Coast To Stop

H1-12

EF3 Delay Tm

H1-12

EF3 Delay Tm

H1-12

EF3 Delay Tm

H1-12

EF3 Delay Tm

Fault Reset

Input

Run

Command

Output

Frequency

Fault Output

(External Fault 3)