P4-15 alternation operation selection, P4-16 alternation time, P4-17 dual zone pid feedback bandwidth range – Yaskawa iQpump Controller Programming Manual User Manual

Page 204: P4-18 run - stop control run time, P4-19 run - stop control stop time, P4-20 run - stop control cycles

Advertising
background image

204

YASKAWA

TM.iQp.07 iQpump Controller Programming Manual

P4-15 Alternation Operation Selection

<0034>

Selects the drive behavior when the internal alternation timer expires.

P4-16 Alternation Time

<0034>

Setting Range:

1.0 ~ 100.0 hrs

Factory Default: 24.0 hrs

Refer to parameter P4-16 in Appendix A for description details.

P4-17 Dual Zone PID Feedback Bandwidth Range

<0034>

Setting Range:

0 ~ 6000.0

Factory Default: 10.0

Refer to parameter P4-17 in Appendix A for description details.

P4-18 Run - Stop Control Run Time

<0034>

Setting Range:

0.0 ~ 6000.0 min

Factory Default: 0.0 min

The Run - Stop Control provides a method to have the drive automatically run and stop for given amounts of time for a given number of
cycles. This feature is primarily used for clearing the sediment out of new water wells.

The Timed Run feature provides a way to perform a “Tank Fill” operation with only a single “low level” switch.

Note: Refer to parameter b1-02 = 5 (Also applies to parameters P4-19 and P4-20).

Table 80 Additional Parameter

P4-19 Run - Stop Control Stop Time

<0034>

Setting Range:

0.0 ~ 6000.0 min

Factory Default: 0.0 min

This parameter sets the amount of time the drive will stop for when the run-stop control is enabled.

P4-20 Run - Stop Control Cycles

<0034>

Setting Range:

0 ~ 1000

Factory Default: 0

This parameter determines how many run-stop cycles the drive will execute before staying stopped.

Setting

Description

0

Wait for Stop

1

Immediate

Parameter

No.

Addr.

Hex

Parameter Name

Digital Operator Display

Description

Range

Default

Menu

Location

b1-02

0181

Run Command Selection
Run Source

Selects the run command input source.
0: Operator - “Hand” and “Off” keys on digital operator
1: Terminals - Contact Closure on Terminal S1
2: Serial Com - RS-485 Terminals R+, R-, S+ and S-
3: Option PCB - Option board connected at 2CN
5: Timed Run

<0034>

0 ~ 3, 5

0

Programming