P5-03 HAND / AUTO During Run Selection

<0032>

Setting Range:

0 ~ 1

Factory Default: 0

Selects if the drive will permit switching between HAND and AUTO modes while running.
0: Disabled
1: Enabled

Switching from HAND to AUTO is not permitted when the drive output frequency is less than the PID minimum speed.

Switching from AUTO to HAND is not permitted when the drive is running in the multiplex mode with auxiliary drives enabled.

P5-04 Hand Key Function Selection

<0032>

Setting Range:

0 ~ 1

Factory Default: 1

Enables or disables the “Hand” key on the digital operator.
0: Disabled
1: Enabled

Parameter

No.

Addr.

Hex

Parameter Name

Digital Operator Display

Description

Range

Default

Menu

Location

P5-02



125

Hand Reference
Hand Reference

Frequency reference used when the Hand Mode is active and P5-01 is
programmed to 1

0.00 ~

120.00 Hz 40.00 Hz Programming

Note:

The MEMOBUS / Modbus address (Addr. Hex) may need to change for this parameter