D1 setpoint and jog references, Setpoint references – Yaskawa iQpump Controller Programming Manual User Manual

Page 47

Advertising
background image

YASKAWA TM.iQp.07 iQpump Controller Programming Manual

47

d1 Setpoint and Jog References

Setpoint References

Setting Range:

0.00 ~ P1-03 Value

Factory Default: 0.00

Figure 1.35

Figure 35. Setpoint and Jog Reference Timing Diagram

* Available only with an LCD operator (JVOP-160).

d1-17 Jog Frequency Reference (LCD Operator Function Only JVOP-160)

Setting Range:

0.00 ~ E1-04 Value

Factory Default: 0.00 Hz

The iQpump drive can be programmed to utilize digital inputs to change between four setpoint and a jog references. It is a two-step
process to set the iQpump drive up for setpoint point and jog references. First, d1-01 through d1-04 and d1-17 must be programmed with
the desired setpoint references and the desired jog reference, respectively. Next, up to three of the drive’s digital inputs (Terminals S3
through S7) need to be programmed (via parameters H1-01 to H1-05) and wired (to normally open contacts) as Multi-step SP1, Multi-
step SP2, and Jog Frequency.

Table 15 Preset Speed Truth Table

As shown in

Table 15 on page 47

, it is possible to use analog inputs in place of Setpoint Reference 1 and Setpoint Reference 2.

Parameter No.

Parameter Name

d1-01

Setpoint Reference 1

d1-02

Setpoint Reference 2

d1-03

Setpoint Reference 3

d1-04

Setpoint Reference 4

Preset Reference

Terminal

programmed as

Multi-step SP1

Terminal

programmed as

Multi-step SP2

Details

1

OFF

OFF

Setpoint Reference 1 (d1-01) or analog input A1

#

(determined by b1-01, see page

47

)

2

ON

OFF

Setpoint Reference 2 (d1-02) or analog input A2

#

(determined by H3-09, see page

47

)

3

OFF

ON

Setpoint Reference 3 (d1-03)

4

ON

ON

Setpoint Reference 4 (d1-04)

# Shown for H3-13 = “0: Main Fref TA1”; A1 and A2 are reversed if H3-13 = “1: Main Fref TA2”

RUN

Multi-step
Reference 1 Input

Multi-step
Reference 2 Input

Closed
Open

Closed
Open

Closed
Open

Closed
Open

Jog Input

Output
Speed

t

d1-01

d1-02

d1-03

d1-04

d1-17

Preset

References

Multi-step
SP 1 Input

Multi-step
SP 2 Input

*

Advertising