YASKAWA TM.iQp.07 iQpump Controller Programming Manual

223

Figure 1.169

Figure 173. De-Scale Function Enabled (P7-01 = 2)

Table 96 Related Parameters

<0034>

Table 97 Function Text

Table 98 Faults

<0034>

Parameter

No.

Addr.

Hex

Parameter Name

Digital Operator Display

Description

Setting

Range

Factory

Setting

Menu

Location

P7-01

84F

Anti-Jam / De-Scale Operation
Selection
Anti-Jam / De-Scale

Selects if the Anti-Jam or De-Scale functions are enabled.
0: Disabled
1: Anti-Jam Enabled
2: De-Scale Enabled
3: Force De-Scale

0 ~ 3

0

Programming

P7-02



850

Anti-Jam / De-Scale Cycle
Count
AJ / DeScaleCycles

Sets the current level (at start) that will trigger the Anti-Jam function.
Set as a percentage of motor rated current.

1 ~ 100

1

Programming

P7-03



851

Anti-Jam Detection Current
Level
A-J Detection 1

Sets the current level (at start) that will trigger the Anti-Jam function.
Set as a percentage of motor rated current.

50 ~ 200%

120%

Programming

P7-04



852

Anti-Jam Detection Time
A-J Det. Time

Sets the amount of time the current has to be above the P7-03 level to
trigger the Anti-Jam function.

0.1 ~ 2.0 s

0.3 s

Programming

P7-05



853

Anti-Jam / De-Scale Frequency
Reference
AJ / DeScale Freq

Sets the speed during the De-Scale operation and during reverse
operation of the Anti-Jam function.

0.00 ~

120.00 Hz 25.00 Hz Programming

P7-06



445

De-Scale Forward Run Time
DeScale Fwd Run

Sets the amount of time the drive will run in forward each cycle
during the De-Scale function.

1 ~ 6000 s

10 s

Programming

P7-07



855

De-Scale Reverse Run Time
DeScale Rev Run

Sets the amount of time the drive will run in reverse each cycle
during the De-Scale function.

1 ~ 6000 s

10 s

Programming

P7-08



856

De-Scale Acceleration Time
DeScale Accel

Sets the amount of time it will take the drive to accelerate from zero
to the De-Scale frequency reference P7-05. (internally limited 0.1 ~
6000.0 s)

0.0 ~ 600.0

s

2.0 s

Programming

P7-09



857

De-Scale Deceleration Time
DeScale Decel

Sets the amount of time it will take the drive to decelerate from zero
to the De-Scale frequency reference P7-05. (internally limited 0.1 ~
6000.0 s)

0.0 ~ 600.0

s

2.0 s

Programming

P7-10



858

De-Scale Pump Run Time
DeScale Time

Sets the number of pump operating hours (pump speed > 0) before a
De-Scale routine will run.

0.1 ~

2000.0 hr.

168.0 hr. Programming

P7-11



859

Anti-Jam Release Time
Anti-Jam Release

Sets the amount of time that the current must be below the P7-03
level in order to resume normal operation.

0.5 ~ 10.0

s

2.0 s

Programming



Denotes that parameter can be changed when the drive is running.

Function Number

Function Name

Digital Operator Display

P7

Anti-Jam / De-Scale

Anti-Jam / De-Scale

Fault Display

Description

Cause

Countermeasures

AJF

Anti-Jam Fault

Anti-Jam Fault

The drive was not able to clear the debris from the impeller in less
than the P4-22 attempts.

Check for proper pump operation
Adjust the P4-23 level or the P4-
22 counts.

Run

Command

P7-05

De-scale Freq.

-P7-05

De-scale Freq.

P

7-

08

P7

-0

9

P

7-0

8

P7

-0

9

P7-06

De-Scale Fwd Run

P7-07

De-Scale Rev Run

P7-06

De-Scale Fwd Run

P7-07

De-Scale Rev Run

P7-06

De-Scale Fwd Run

P7-07

De-Scale Rev Run

P4-04

Thrust

C

1-

01

Output

Frequency

De-Scale

Alarm

Normal Operation

Resumes

Cycle

1

Cycle

2

Cycle

3

Run command issued

for the number of times

programmed into P7-10

.

During the de-scale operation, all other iQPump functions are disabled:

PI Control, Pre-Charge, Thrust, etc...

De-scale Function Enabled: P7-01 = 2

P7-02 = 3

A-J Cycle Count

C1-02

P4-06

Thrust