P6-02 water flow units, P6-03 flow accumulation reset – Yaskawa iQpump Controller Programming Manual User Manual

Page 216

Advertising
background image

216

YASKAWA

TM.iQp.07 iQpump Controller Programming Manual

Table 93 Multi-Function Output Settings (H2-xx)

<0034>

Table 94 Faults

<0034>

Table 95 Alarms

<0034>

P6-02 Water Flow Units

Setting Range:

0 ~ 4

Factory Default: 0

P6-03 Flow Accumulation Reset

Setting Range:

0 ~ 65535

Factory Default: 0

Refer to parameter P6-03 in Appendix A for description details.

Setting

Description

4E

Low Flow
Closed: During the “Low Flow Fault” condition OR
Closed: During a low flow condition as set by P6-04 ~ P6-06 (includes “Low Flow Alarm”).

4F

<2>

Accum Level

<2>

Closed: Accumulated level has exceeded the P6-09 and P6-10 setting OR
Closed: During the “Accum Level” Fault.

56

<3>

High Flow

<3>

Closed: During the “High Flow Fault” condition OR
Closed: During a high flow condition as set by P6-04 ~ P6-06 (includes “High Flow Alarm”)

Fault Display

Description

Cause

Countermeasures

LOWFL

Low Flow

Low flow has been detected by the flow
meter.

Not enough flow, or incorrect “P6” settings

ACCUM

Accum Level

Accumulated Level

Accumulated level has exceeded the P6-09 and P6-10 settings.

Reset the accumulated level
(P6-03 or via digital input)

OPE13

Terminal A1

Programming error

Terminal A1 is being assigned to more than one of the following
functions.

- Frequency Reference (b1-01 = 1)
- Dual Zone PI is enabled (b5-01 = 2)
- Flow Meter Enabled (P6-01 > 0)
- Level Control Enabled (P8-01 =1)

Reprogram b1-01, b5-01, P6-01
or P8-01.

OPE14

FlowMtrNotEnable

Programming error

The sleep level type has been set to “FlowMtr-Term A1”
(P2-01 = 4) but the flow meter function is not enabled
(P6-01 = 0.0)

Reprogram P2-01 or P6-01.

HIFLO

High Flow

High flow has been detected by the flow
meter.

Too much flow or incorrect “P6” settings.

Alarm Display

Description

Cause

Countermeasures

LOWFL

Low Flow

Low flow has been detected by the flow
meter.

Not enough flow, or incorrect “P6” settings

ACCUM

Accum Level

Accumulated Level

Accumulated level has exceeded the P6-09 and P6-10 settings.

Reset the accumulated level
(P6-03 or via digital input)

HIFLO

High Flow

High flow has been detected by the flow
meter.

Too much flow or incorrect “P6” settings.

Setting

Description

0

U.S. Gallons / min (GPM)

1

U.S. Gallons / hr (GPH)

2

U.S. Barrels / min (BPM)

3

U.S. Barrels / hr (BPH)

4

U.S. Barrels / Day (BPD)