N3 high-slip braking – Yaskawa iQpump Controller Programming Manual User Manual

Page 132

Advertising
background image

132

YASKAWA

TM.iQp.07 iQpump Controller Programming Manual

n3 High-Slip Braking

n3-01 High-Slip Braking Deceleration Frequency

Setting Range:

1.0 ~ 20.0%

Factory Defaults: 5%

Sets how aggressively the drive decreases the output frequency as it stops the motor. If overvoltage (OV) faults occur during HSB, this
parameter may need to be increased.

Note: Function Deactivated

n3-02 High-Slip Braking Current Limit

Setting Range:

100.0 ~ 200.0%

Factory Defaults: 150%

Sets the maximum current to be drawn during a HSB stop. Higher n3-02 settings will shorten motor stopping times but cause increased
motor current and therefore, increased motor heating.

Note: Function Deactivated

n3-03 High-Slip Braking Dwell Time at Stop

Setting Range:

0.00 ~ 10.00 s

Factory Defaults: 1.0 s

Sets the amount of time the drive will dwell at E1-09 (Minimum Frequency). If this time is set too low, the machine inertia can cause the
motor to rotate slightly after the HSB stop is complete and drive output is shut off.

Note: Function Deactivated

n3-04 High-Slip Braking Overload Time

Setting Range:

30.0 ~ 1200.0 s

Factory Defaults: 40 s

Sets the time required for a HSB Overload Fault to occur when the drive output frequency does not change for some reason during a HSB
stop. Normally this does not need to be adjusted.

Note: Function Deactivated