T1 Auto-Tuning

T1-02 Motor Rated Power

Setting Range:

0.00 ~ 650.00 kW

Factory Default: Model Dependent

Refer to parameter T1-02 in Appendix A for description details.

T1-04 Motor Rated Current

Setting Range:

Model Dependent

Factory Default: Model Dependent

Auto tuning is recommended to achieve optimum performance. In addition, the iQpump drive requires Line-To-Line Resistance auto-
tuning before it can properly perform the Estimated Speed Search method. This method of speed search allows for bi-directional speed
search. The T1 parameters are found under the Auto-Tuning menu.

To perform auto-tuning follow these steps:

1. T1-02 should be left at the default value (the last 3 digits of the iQpump drive model number).
2. In T1-04, enter the Full Load Amps (FLA) as stamped on the motor’s nameplate.
3. Press the INCREASE key once to display this:

4. If ready, press the HAND key once to start auto-tuning. This process will last for approximately 15 seconds. Once auto-tuning is

finished, the digital operator will display this:

5. To exit the Auto-Tuning menu, press the MENU key once.

Note: It is possible to a get a “Data Invalid” error if the either T1-02 or T1-04 fall outside the range of what the iQpump drive

will accept as reasonable levels for the programmed size of the iQpump drive (o2-04).

Tuning Ready?
Press HAND key

-ATUNE-

Rdy

Auto: ATUNE

0 Hz/ 0.00A

-ATUNE-

Tune Successful

0 Hz/ 0.00A