Figure 153. utility delay: cycle run command, Figure 154. utility delay: run command – Yaskawa iQpump Controller Programming Manual User Manual

Page 200

Advertising
background image

200

YASKAWA

TM.iQp.07 iQpump Controller Programming Manual

Figure 1.149

Figure 153. Utility Delay: Cycle Run Command

<0034>

Figure 1.150

Figure 154. Utility Delay: Run Command

<0034>

Figure 1.151

Figure 155. Utility Delay: Undervoltage and Overvoltage

<0034>

Table 75 Related Parameters

<0034>

Parameter

No.

Addr.

Hex

Parameter Name

Digital Operator Display

Description

Range

Default

Menu

Location

P4-11



82A

Utility Start Delay
Utility Delay

Sets the amount of time the drive will delay starting if a run
command is present at power up. A setting of 0.0 disables this
function.

0.0 ~

1000.0 min 0.2 min Programming



Denotes that parameter can be changed when the drive is running.

Incoming

Power

Output

Frequency

1 Sec.

Run

Command

P4-11

Utility Start Delay Time

P1-05

S-Lvl Delay Time

Incoming

Power

Output

Frequency

1 Sec.

Run

Command

P1-05

S-Lvl Delay Time

P4-11

Utility Start Delay Time

1 Sec.

DC Bus

completely

discharged

P1-05

S-Lvl Delay Time

DC Bus
Voltage

Overvoltage Level

Undervoltage Level

Output

Frequency

Run

Command

P4-11

Utility Start Delay Time

L5-03

Max Restart Time

P4-11

Utility Start Delay Time