The factory defaults of the following parameters may be changed when the setting of o2-04 is changed:

• b8-04 (Energy Saving Coefficient Value)
• C6-02 (Carrier Frequency Selection)
• E2-01 (Motor Rated Current)
• E2-03 (Motor No-Load Current)
• E2-05 (Motor Line-to-Line Resistance)
• L2-02 (MPL Ride-Thru Time)
• L2-03 (MPL Minimum Base Block Time)
• L2-04 (MPL Voltage Recovery Ramp Time)
• L8-02 (Overheat Pre-Alarm Level)
• L8-06 (Input Phase Loss Detection Level)

o2-05 Frequency Reference Setting Method Selection

The factory default setting of the Frequency Reference Setting Method parameter (o2-05 = “1: Enabled”) dictates that when setting a
Speed Command via the digital operator (“Hand” mode), it is not necessary to press the DATA / ENTER key before the iQpump drive
will begin to accelerate or decelerate to the new set speed. This is referred to as MOP (Motor Operated Potentiometer) type functionality.
When o2-05 = “1: Enabled,” the speed command is stored to memory 5 seconds after the INCREASE or DECREASE keys are released.

When o2-05 = “0: Disabled,” the digital operator INCREASE and DECREASE keys will change the speed command but the iQpump
drive will not accelerate or decelerate to the new speed command until the DATA / ENTER key is pressed. In order to change the Speed
Command in the HAND mode, U1-01 must be the top monitor and then the ENTER key must be pressed in order to access the Speed
Command function. This in not to be confused with pressing the ENTER key in order to achieve a change in speed using the INCREASE
and DECREASE keys, which is the subject of parameter o2-05.

22P2

3

42P2

23

23P7

4

43P7

24

27P5

6

45P5

26

2011

7

47P5

27

2015

8

49P0

3C

2018

9

4011

28

2022

A

4015

29

2030

B

4018

2A

2037

C

4022

2B

2045

D

4024

3D

2055

E

4030

2C

2075

F

4037

2D

2090

10

4045

2E

2110

11

4055

2F

4075

30

4090

31

4110

32

4160

34

4185

35

4220

36

4300

37

Setting

Description

0

Disabled (

factory default

)

1

Enabled

208-230 / 240 Vac

480 Vac

Model Number

Proper

o2-04 Setting

Model Number

Proper

o2-04 Setting