L3-05 stall prevention selection during running, L3-06 stall prevention level during running – Yaskawa iQpump Controller Programming Manual User Manual

Page 121

Advertising
background image

YASKAWA TM.iQp.07 iQpump Controller Programming Manual

121

L3-05 Stall Prevention Selection During Running

L3-06 Stall Prevention Level During Running

Setting Range:

30 ~ 200% of the iQpump drive rated output current

Factory Default: 120% of the iQpump drive rated output current

The Stall Prevention During Running function will attempt to avoid an iQpump drive OC fault occurrence while the iQpump drive is
operating at a constant speed. If L3-05 = “0: Disabled,” the iQpump drive may fault if the load increases sufficiently to cause the output
current to reach the OC fault level (180% of the iQpump drive rated output current).

If L3-05 = “1: General Purpose,” the iQpump drive is outputting a constant speed, and the drive’s output current level exceeds the level set
by parameter L3-06 for more than 100 ms the iQpump drive will begin to decelerate at the rate specified by parameter C1-02. The
iQpump drive will continue to decelerate until the output current level drops below the L3-06 level (less a 2% hysteresis). Once the output
current drops below the L3-06 – 2% level the iQpump drive will begin to accelerate at the currently active acceleration rate (either C1-01
or C1-03).

If L3-05 = “2: Decel Time 2,” the iQpump drive will function as described above except C1-04 will be used instead of C1-02 as the
deceleration rate used when the output current exceeds L3-06 for more than 100 ms.

The following

Figure 103.

demonstrates acceleration when L3-05

≠0.

Figure 1.99

Figure 103. Time Chart for Stall Prevention Level During Running

The L3-06 parameter is set as a percentage of the iQpump drive rated output current. If the iQpump drive still faults when L3-05

≠0, then

either lower the L3-06 or adjust the C1-02 or C1-04 settings for a quicker deceleration.

Setting

Description

0

Disabled

1

Decel Time 1 (

factory default

)

2

Decel Time 2

a

L3-06

t

Output

Frequency

Output

Current

b

a

- Decel time

C1-02 or C1-04.

b

– Active accel time

t

b

a

a - Decel time

C1-02 or C1-04

b - Active Accel time

TIME

Advertising