YASKAWA TM.iQp.07 iQpump Controller Programming Manual

97

H5 Serial Communications Setup

This section explains the individual functions used in special applications involving MEMOBUS / Modbus Communications.

Communication Specifications

The MEMOBUS / Modbus communication specifications are shown below:

Table 34 MEMOBUS / Modbus Communication Specifications

MEMOBUS / Modbus Communication Configuration

MEMOBUS / Modbus communication is configured using 1 master (PLC) and a maximum of 31 slaves. Serial communication between
master and slave is normally initiated by the master and responded to by the slaves.

The master performs serial communication with one slave at a time. Consequently, the slave address of each slave must be individually
set, so that the master can perform serial communication using that address. Slaves receiving commands from the master perform the
specified functions, and send a response back to the master.

Figure 1.87

Figure 86. Example of Connections between Master and Drive

Communication Connection Terminal

MEMOBUS / Modbus communication uses the following terminals: S+, S-, R+, and R-. The terminating resistance must be turned ON
only if the iQpump drive is at the very end of the Serial Communication chain. Set the terminating resistance by turning ON pin 1 of
switch S1 On the drives terminal board. Switch S1 is located directly above the left most relay module.

Figure 1.88

Figure 87. Communication Connection Terminals and Terminating Resistance

Item

Specifications

Interface

RS-422, RS-485

Communications Cycle

Asynchronous (Start-stop synchronization)

Communications Parameters

Baud rate:

Select from 1200, 2400, 4800, 9600, and 19200 bps.

Data length:

8 bits fixed

Parity:

Select from even, odd, or none.

Stop bits:

1 bit selected

Communications Protocol

MEMOBUS / Modbus

Number of Connectable Units

31 units max.

Master

iQpump

iQpump

iQpump

Slaves

Terminating resistance (1/2W, 110 Ohms)

RS-422A
or RS-485

Switch

S1

O
F
F

1

Terminating
resistance on

DIP Switch S1 located on
terminal board.

2

1