YASKAWA TM.iQp.07 iQpump Controller Programming Manual

215

Table 90 Function Text

Table 91 Monitors

<0034>

Table 92 Multi-Function Input Setting (H1-xx)

<0034>

P6-07

846

Low Flow Select
Low Flow Sel

Sets the behavior of the drive when a “Low Flow” condition is
detected.

0: No Display
1: Alarm Only
2: Fault
3: Auto-Restart (time set by P6-08)

0 ~ 3

1

Programming

P6-08

847

Low Flow Auto-Restart Time
LowFlow Restrt

Sets the amount of time the drive will wait before attempting an auto-
restart of the “Low Flow” fault. Effective only when P6-07 = 3.

0.1 ~

6000.0 min 3.0 min Programming

P6-09



848

Accumulation Level Fine
Accum Lvl Fin

e

Sets the accumulated volume that will trigger the Accum Level
alarm, Accum Level fault, or Accum Level digital output. Total
Accum Level can be calculated as follows: Total Accum Level = P6-
10 * 1000 + P6-09.

0.0 ~

999.0 gal

0.0

Programming

P6-10



849

Accumulation Level Course
Accum Lvl Course

Sets the accumulated volume that will trigger the Accum Level
alarm, Accum Level fault, or Accum Level digital output. Total
Accum Level can be calculated as follows: Total Accum Level = P6-
10 * 1000 + P6-09.

0 ~

61036 kgl

0

Programming

P6-11



84A

Accumulation Behavior
Accum Behavior

Sets how the drive will respond when the accumulated volume
reaches the P6-09 and P6-10 level.

0: No Display
1: Alarm Only
2: Fault
3: Fault - Auto Flow Accum Reset

0 ~ 3

1

Programming

P6-12



84B

High Flow Level
High Flow Level

If the drive is running, and the flow goes above this level for more
than the P6-13 time, a High Flow fault or alarm will occur. A setting
of 0 disables the high flow detection.

0.0 ~

6000.0

(*n1)

0.0

Programming

P6-13



84C

High Flow Detection Delay Time
High Flow Time

Sets the amount of time the flow rate must be above the P6-12 level
before a High Flow condition is detected.

1 ~ 6000 s

10

Programming

P6-14

84D

High Flow Select
High Flow Sel

Sets the behavior of the drive when a “High Flow” condition is
detected.

0: No Display
1: Alarm Only
2: Fault
3: Auto-Restart (time set by L5-03)

0 ~ 3

1

Programming



Denotes that parameter can be changed when the drive is running.

(*n1) Displayed units are determined by parameter P6-02.

Function Number

Function Name

Digital Operator Display

P6

Flow Meter Setup

Flow Meter Setup

Monitor

No.

Addr.

Hex

Monitor Name

Digital Operator Display

Description

U1-95

725

Flow Rate

Flow Rate

Displays the flow rate, based upon the voltage present on Terminal A1 and parameters P6-01 and P6-02. A
two second 1st order filter will be applied to this monitor.

U1-96

72A

Volume Accumulated (Fine)

Volume (Fine)

Displays the volume that has been measured by terminal A1. Total volume can be calculated as follows:
Total Volume = U1-97 * 1000 + U1-96.

Value retained in EEPROM.

U1-97

72B

Volume Accumulated (Course)

Volume (Course)

Displays the volume that has been measured by terminal A1. Total volume can be calculated as follows:
Total Volume = U1-97 * 1000 + U1-96.

Value retained in EEPROM.

Setting

Description

75

Reset Accum
Closed: Volume accumulated will be reset to zero (and held at zero if digital input remains closed).

Parameter

No.

Addr.

Hex

Parameter Name

Digital Operator Display

Description

Setting

Range

Factory

Setting

Menu

Location