Carrier frequency limit – Yaskawa iQpump Controller Programming Manual User Manual

Page 46

Advertising
background image

46

YASKAWA

TM.iQp.07 iQpump Controller Programming Manual

Figure 1.34

Figure 34.

Carrier Frequency Parameter Factory Defaults

Carrier Frequency Limit

Setting Range:

0.4 ~ 10.0 kHz

Factory Default: Model Dependent

Parameter No.

Parameter Name

C6-03

Carrier Frequency Upper Limit

C

C arrier F requency P arameter F actory Defaults :

208V – 240V Drives

480V Drives

Model

CIMR-P7

C6-02

Carrier

Frequency

(kHz)

C6-03

Carrier Frequency

(kHz)

Model

CIMR-P7

C6-02

Carrier

Frequency

(kHz)

C6-03

Carrier Frequency

(kHz)

20P4 3

8.0

kHz* 40P4 3 8.0

kHz*

20P7 3

8.0

kHz* 40P7 3 8.0

kHz*

21P5 3

8.0

kHz* 41P5 3 8.0

kHz*

22P2 3

8.0

kHz* 42P2 3 8.0

kHz*

23P7 3

8.0

kHz* 43P7 3 8.0

kHz*

25P5 3

8.0

kHz* 44P0 3 8.0

kHz*

27P5 3

8.0

kHz* 45P5 3 8.0

kHz*

2011 3

8.0

kHz* 47P5 3 8.0

kHz*

2015 3

8.0

kHz* 49P0 3 8.0

kHz*

2018 3

8.0

kHz* 4011 3 8.0

kHz*

2022 3

8.0

kHz* 4015 3 8.0

kHz*

2030 3

8.0

kHz* 4018 3 8.0

kHz*

2037 2

5.1

kHz

4022 3 8.0

kHz*

2045 2

5.1

kHz

4024 3 8.0

kHz*

2055 3

8.0

kHz* 4030 3 8.0

kHz*

2075 1

2.0

kHz

4037 3 8.0

kHz*

2090 1

2.0

kHz

4045 3 8.0

kHz*

2110 1

2.0

kHz

4055 2

5.1

kHz

4075 2 5.1

kHz

4090 3 8.0

kHz*

4110 2 5.1

kHz

4132 2 5.1

kHz

4160 2 5.1

kHz

4185 1 2.0

kHz

4220 1 2.0

kHz

4300 1 2.0

kHz

* = when an option card is installed, C6-03 max is 7.0 kHz.

Advertising