P4-08 Protection Fault Auto Restart Enable

<0032>

Setting Range:

0 ~ 7

Factory Default: 0

Setting to enable / disable Auto Restart for the following iQpump protection faults:

SP: Not Maintaining Setpoint (P1-11)
LOP: Loss of Prime (P1-16)
POC: Pump Over Cycling (P2-08)

Note: Parameter L5-01 needs to be set to “1” and program L5-03 needs to be set to the applicable time.

Figure 1.148

Figure 152. System Fault Auto-Restart Fault Counter

Setting

POC

LOP

SP

0:

Disable

Disable

Disable

1:

Disable

Disable

Enable

2:

Disable

Enable

Disable

3:

Disable

Enable

Enable

4:

Enable

Disable

Disable

5:

Enable

Disable

Enable

6:

Enable

Enable

Disable

7:

Enable

Enable

Enable

System

Auto-

Restart

Counter

Cleared

System Fault Restarts

:

Drive 1

Drive 1

Drive 2

Drive 2

Local Fault Restarts :

Local Fault Restarts :

Auto-Restarting ?

Auto-Restarting ?

NMS

Fault

/ Message Display

Fault / Message Display

Fault

NMS

EF3

LFB/LW

Net Pump Err

Manual

Fault Reset

Auto

Fault Reset

L5-01 = 5
P4-08 = 7 (

POC=Y LOP=Y SP=Y)

P9-22 = 3

Net Pump Err

EF3

1

0

0

0

2

1

2

2

2

2

3

2

3

3

1

0

0

0

1

1

1

1

1

0

0

0

0

0

1

0

0

0

0

1

0

1

1

1

0

0

0

0

0

0

0

1

1

1

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

1

1

1

No system fault for 10 mins

NMS

HFB/HW

Net Pump Err

EF3

Net Pump Err

Net Pump Err

Auto

Fault Reset

Auto

Fault Reset

Auto

Fault Reset

Auto

Fault Reset

Auto

Fault Reset

No local fault for 10 mins

Advertising