Monitor Data

The following table shows the monitor data. Monitor data can only be read.

Table 38 Monitor Data

Register Hex

Contents

0020

Drive status

Bit 0

Running 1: Running 0: Stopped

Bit 1

Reverse operation 1: Reverse operation 0: Forward operation

Bit 2

Drive startup complete 1: Completed 0: Not completed

Bit 3

Fault1: Fault

Bit 4

Data setting error1: Error

Bit 5

Multi-function digital output 1 (terminal M1 - M2) 1: ON 0: OFF

Bit 6

Multi-function digital output 2 (terminal M3 - M4) 1: ON 0: OFF

Bit 7

Not used

Bits 8 ~ F

Not used

0021

Fault details

Bit 0

Overcurrent (OC) Ground fault (GF)

Bit 1

Main circuit overvoltage (OV)

Bit 2

Drive overload (OL2)

Bit 3

Drive overheat (OH1, OH2)

Bit 4

Not used

Bit 5

Fuse blown (PUF)

Bit 6

PI feedback reference lost (FbL)

Bit 7

External error (EF, EFO)

Bit 8

Hardware error (CPF)

Bit 9

Motor overload (OL1) or overtorque 1 (OL3) detected

Bit A

PG broken wire detected (PGO), Overspeed (OS), Speed deviation (DEV)

Bit B

Main circuit undervoltage (UV) detected

Bit C

Main circuit undervoltage (UV1), control power supply error (UV2), inrush prevention circuit error (UV3), power loss

Bit D

Missing output phase (LF)

Bit E

MEMOBUS / Modbus communications error (CE)

Bit F

Operator disconnected (OPR)

0022

Data link status

Bit 0

Writing data

Bit 1

Not used

Bit 2

Not used

Bit 3

Upper and lower limit errors

Bit 4

Data integrity error

Bits 5 ~ F

Not used

0023

Frequency

reference

U1-01

0024

Output

frequency

U1-02

0025

Output voltage

reference

U1-06

0026

Output current U1-03

0027

Output power

U1-08

0028

Torque reference U1-09

0029

Not used

002A

Not used