YASKAWA TM.iQp.07 iQpump Controller Programming Manual

41

C1 Accel / Decel

Acceleration Times

Setting Range:

0.0 ~ 6000.0 s

Factory Defaults: C1-01 20.0 s

C1-02, C1-03 and C1-04 10.0 s
C1-05 and C1-06 50.0 s

C1-01 (Acceleration Time 1) sets the time to accelerate from zero to maximum speed (E1-04). C1-02 (Deceleration Time 1) sets the time
to decelerate from maximum speed to zero. C1-01 and C1-02 are the factory default active accel / decel “pair”. Another accel / decel pair
(C1-03 and C1-04) exists that can be activated by a multi-function digital input (H1-0x = 7), or specified by a switch over frequency as
programmed in parameter C1-11.

C1-05 (Acceleration Time 3) and C1-06 (Deceleration Time 3) are used during the multiple pumping operation. Refer to P3-12 for more
details.

Acceleration Time: This is the time it takes to accelerate from 0 Hz to Maximum Output Frequency defined by parameter E1-04.

Deceleration Time: This is the time it takes to decelerate from Maximum Output Frequency defined by parameter E1-04 to 0 Hz.

Example: C1-01 Acceleration Time 1 programmed for 30 seconds, E1-04 Maximum Output Frequency set to 60 Hz. It will take the
iQpump Controller 20 seconds to accelerate from 0 to 40 Hz (40 Hz ÷ 60 Hz x 30 s = 20 s).

Example: C1-02 Deceleration Time 1 programmed for 50 seconds, E1-04 Maximum Output Frequency set to 60 Hz. It will take the
iQpump Controller 10 seconds to decelerate from 60 to 30 Hz (30 Hz ÷ 60 Hz x 50 s = 25 s).

• Thrust Bearing Operation uses a separate acceleration time defined by parameter P4-04. Once Thrust frequency is reached, the iQpump

drive returns to its normal acceleration time set by C1-01.

• Pre-charge mode uses C1-01 as its acceleration time.
• Hand Mode Operation uses C1-01 and C1-02 for acceleration and deceleration time.
• Auto Mode can use acceleration time C1-05 and deceleration time C1-06, depending on parameter P3-12 setting (see section.

P3-12

Delta Setpoint Feedback Acc / Dec Changeover on page 183

.)

C1-09 Fast Stop Time

Setting Range:

0.0 ~ 6000.0 s

Factory Default: 10.0 s

A special deceleration parameter is available for use with emergency or fault operations. Parameter C1-09 will set a special deceleration
that can be operated by closing a digital input configured as H1-0x = 15 or H1-0x = 17. A digital input configured as H1-0x = 15 will look
for a switch closure before initiating the Fast Stop operation. A digital input configured as H1-0x = 17 will look for the switch opening
before initiating the Fast Stop operation.

Unlike a standard deceleration time, once the Fast Stop operation is initiated even momentarily, the iQpump drive cannot be re-operated
until the deceleration is complete, the Fast Stop input is cleared, and the Run command is cycled.

The C1-05 (Acceleration Time 3) and C1-06 (Deceleration Time 3) are used during the multiplex pumping operation. Refer to P3-12 for
more details.

Parameter No.

Parameter Name

C1-01

Acceleration Time 1

C1-02

Deceleration Time 1

C1-03

Acceleration Time 2

C1-04

Deceleration Time 2

C1-05

Acceleration Time 3

C1-06

Deceleration Time 3