Memobus / modbus data tables, Reference data – Yaskawa iQpump Controller Programming Manual User Manual

Page 103

Advertising
background image

YASKAWA TM.iQp.07 iQpump Controller Programming Manual

103

MEMOBUS / Modbus Data Tables

The data tables are shown below. The types of data are as follows: Reference data, monitor data and broadcast data.

■

Reference Data

The reference data table is shown below. Reference data can be read and written to.

Table 37 Reference Data

Register Hex

Contents

0000

Reserved

0001

Sequence Control

Bit 0

Run Forward 1: Run 0: Stop

Bit 1

Run Reverse 1: Run 0: Stop

Bit 2

External fault1: Fault (EFO)

Bit 3

Fault reset1: Reset command

Bit 4

ComNet

Bit 5

ComCtrl

Bit 6

Multi-function digital input command 3

Bit 7

Multi-function digital input command 4

Bit 8

Multi-function digital input command 5

Bit 9

Multi-function digital input command 6

Bit A

Multi-function digital input command 7

Bits B ~ F

Not used

0002

Frequency reference (Set units using parameter o1-03)

0003 ~ 0005

Not used

0006

PI Setpoint

0007

Analog output 1 setting (-11 V = 726 ~ 11 V = 726)

→ 10 V = 660

0008

Analog output 2 setting (-11 V = 726 ~ 11 V = 726)

→ 10 V = 660

0009

Multi-function contact output setting

Bit 0

Digital output 1 (Terminal M1-M2) 1: ON 0: OFF

Bit 1

Digital output 2 (Terminal M3-M4) 1: ON 0: OFF

Bit 2

Not Used

Bits 3 ~ 5

Not used

Bit 6

Set fault contact (terminal MA-MC) output using bit 7. 1: ON 0: OFF

Bit 7

Fault contact (terminal MA-MC) 1: ON 0: OFF

Bits 8 ~ F

Not used

000A ~ 000E

Not used

000F

Reference selection settings

Bit 0

Not used

Bit 1

Input PI Setpoint 1: Enabled 0: Disabled

Bits 3 ~ B

Not used

C

Broadcast data terminal S5 input 1: Enabled 0: Disabled

D

Broadcast data terminal S6 input 1: Enabled 0: Disabled

E

Broadcast data terminal S7 input 1: Enabled 0: Disabled

F

Not used

Note: Write 0 to all unused bits. Also, do not write data to reserved registers.