Yaskawa iQpump Controller Programming Manual User Manual
Page 169

YASKAWA TM.iQp.07 iQpump Controller Programming Manual
169
Figure 1.120
Figure 124.
Figure 1.121
Figure 125.
Figure 1.122
Figure 126.
The sleep function can be active during the following conditions:
• When P2-20 is set to 0 or 3
<0034>
(disabled), the output frequency must be greater than the Sleep Level (P2-02).
• When P2-20 is greater than P2-02, the output frequency must be greater than Alternative Sleep Activation Level (P2-20). See
• When P2-20 is greater than 0 and less than P2-02, the output frequency must be greater than Alternative Sleep Activation Level
(P2-20). See
• When P2-20 is greater than 0 and less than P2-02, the output frequency must be greater than Alternative Sleep Activation Level
(P2-20) and Sleep Level (P2-02). See
A value of 0 programmed in P2-20 will disable this function.
• P2-01 = 0: Display based on “Hz”
<0034>
P1-06
SLEEP MODE
SLEEP PERMITTED
P2-02
P2-20
P2-03
P1-06
SLEEP PERMITTED
P2-02
P2-20
P2-03
SLEEP MODE
P1-06
SLEEP MODE
SLEEP PERMITTED
P2-02
P2-20
P2-03