Figure 184, Figure 185 – Yaskawa iQpump Controller Programming Manual User Manual

Page 248

Advertising
background image

248

YASKAWA

TM.iQp.07 iQpump Controller Programming Manual

Figure 1.180

Figure 184. Drive Requests for a New Lead Drive using Output Frequency (P9-08 = 0)

Figure 1.181

Figure 185. Drive Requests for a New Lead Drive using Feedback (P9-08 = 1)

PID Active

Set-Point

Feedback

Output Frequency

Lag Fixed Speed P9-06

Add Pump Level P9-09

Lag Fixed Delay

P9-07

Lag Fixed Delay

P9-07

Add Delay Time

P9-11

Add Delay Time

P9-11

Add Delay Time

P9-11

Add Delay Time

P9-11

PumpNet Status1 U1-55 bit 4:

Requesting for Staging (next lead)

PumpNet Control1 U1-59 bit 1:

Run as Lag Drive

PumpNet Control1 U1-59 bit 2:

Run as Lead Drive

Set-Point

Feedback

Add Delay Time

P9-11

Add Delay Time

P9-11

PumpNet Status1 U1-55 bit 4:

Requesting for Staging (next lead)

PumpNet Control1 U1-59 bit 1:

Run as Lag Drive

PumpNet Control1 U1-59 bit 2:

Run as Lead Drive

Add Pump Delta

P9-10

PID Active