YASKAWA TM.iQp.07 iQpump Controller Programming Manual

229

Figure 1.173

Figure 177. Constant Pressure with Well Draw Down Control - Maintain Flow and Pressure

Table 102 Related Parameters

Parameter

No.

Addr.

Hex

Parameter Name

Digital Operator Display

Description

Setting

Range

Factory

Setting

Menu

Location

P8-01

860

Pressure and Level Control
Select
Pres&Lvl Control

Enables / Disables the Constant Pressure With Well Draw Down
Control.

0: Disabled
1: Enabled

0 ~ 1

0

Programming

P8-02

861

Water Level Scaling
Water Lvl Scale

Sets the full scale (20 mA) output of the pressure transducer that is
connected to Terminal A1.

5 ~ 500 psi

100

Programming

P8-03



862

Water Level Setpoint
Water Lvl Setpnt

Sets the amount of water above the sensor that the drive will attempt
to regulate to.

0.0 ~

1200.0 ft

20.0

Programming

P8-04



863

Minimum Water Level
Min Water Level

When the amount of water above the sensor drops below this level
for more than the P2-03 time, the drive will go to sleep.

0.0 ~

1200.0 ft

10.0

Programming

P8-05



864

Wake-Up Water Level
Wake-Up Level

If the drive has been forced to sleep based upon the minimum water
level (P8-04), the water will have to go above this level for more than
the P1-05 time in order to wake up.

0.0 ~

1200.0 ft

30.0

Programming

P8-06



865

Level Control Minimum Speed
Level Min Spd

This parameter sets the minimum speed the drive will be allowed to
run at when the drive is controlling the water level. When the drive is
controlling pressure or this parameter is set less than P1-06 & P4-05,
P1-06 & P4-05 will be used as the minimum speed.

0.00 ~

120.0 Hz

0.00

Programming

P8-07



866

Low Level Detection Level
Low Level Detect

When the amount of water above the sensor drops below this level
for more than the P8-08 time, the drive will respond depending on the
P8-09 setting. A setting of 0.0 disables this detection.

0.0 ~

1200.0 ft

0.0

Programming

P8-08



867

Low Level Detection Time
Delay
Low Lvl Det Tm

Sets the amount of time delay that the water level must drop below
the P8-07 level before the drive will react.

0.0 ~

300.0 min

0.1

Programming

P8-09

868

Low Level Behavior
Low Lvl Behavior

Sets how the drive will respond when the water level in the well
drops below the P8-07 level for more than the P8-08 time.

0: No Display (Digital Output Only)
1: Alarm Only
2: Fault

0 ~ 2

1

Programming

P8-10



869

Level Control Proportional Gain
Lvl Ctrl P Gain

Sets the proportional gain for the water level control.

0.00 ~

25.00

2.00

Programming

P8-11



86A

Level Control Integral Time
Lvl Ctrl I Time

Sets the integral time for the water level control. A setting of zero
disables the water level control integrator.

0.0 ~

360.0 s

5.00

Programming



Denotes that parameter can be changed when the drive is running.

W ater Level

T erm A1

(U 1-98)

Pressure F eedback

T erm A2

(U 1-91)

Output F requency

(U 1-02)

1

4

1

1

Pressure Control – Enough w ater in w ell to m aintain pressure & flow . If w ater level drops below P8-04 level, drive goes to sleep .

4

Drive Sleeping – W aiting for w ell to recharge and level to go above W ake-U p Level (P8-05).

Wake-Up Level (P8-05) > Level Control Minimum Level (P8-04) > Level Control Setpoint (P8-03)

P8-05

P8-04

P8-03

P2-03

P1-05

d1-0x

Wake-Up Level

Level Control Minimum Level

Level Control Setpoint

Sleep Delay Time

Start Delay Time

Pressure Setpoint