Rockwell Automation 5370-CVIM2 Module User Manual
Page 16

Chapter 1
Hardware Connection and Powerup Check
1–4
Attach the color–coded leads on the DC cable to the external DC power
supply as follows:
1. Connect the triple red leads to the DC power supply’s main “+ output”
terminal.
2. If your DC power supply has a “+ sense” terminal, connect the single red
lead to that terminal. Otherwise, connect the single red lead to the “+
output” terminal, along with the triple red leads.
3. Connect the triple black leads to the DC power supply’s main “– output”
terminal.
4. If your DC power supply has a “– sense” terminal, connect the single
black lead to that terminal. Otherwise, connect the single black lead to
the “– output” terminal, along with the triple black leads.
5. Connect the molded plug on the other end of the DC power supply cable
to the Pyramid Integrator power supply front panel jack labeled “
Fan
Chassis
.”
6. If your application has a fan chassis and you are using the 5120–CP2
cable, connect the smaller molded plug to the jack in the fan chassis.
Finally, attach a line cord or other AC power supply cables to the DC power
supply, as appropriate for your installation.
NOTE: Do not apply AC power to the DC power supply yet.