Chapter 7

Inspection Tools

7–99

In Figure 7.83, four “morph passes” have occurred, with the result that all of
the horizontal lines are eliminated.

Figure 7.83 Example: Image Tool (Four Morph Passes)

Note that the only effect on the vertical lines has been to shorten them.

This section discusses the expanded inspection results that are available to a
math tool formula from an image tool. As Figure 7.84 shows, the expanded
inspection results for an image tool appear in one list.

Figure 7.84 Expanded Results Lists For Image Tools in Math Formulas

Execute
Pass
Warn
Fail
Total
Faults

Here is a brief definition and explanation of each of the expanded result
types listed in Figure 7.84.

Execute –– This returns a

1.000

when the tool has executed its inspection

task, and

0.000

for all other conditions.

Pass –– This returns a

1.000

when the tool has passed its inspection task,

and

0.000

for all other conditions.

Warn –– This always returns a

0.000

.

Image Tool Inspection