Related function blocks, Error description – Yaskawa MotionWorks IEC User Manual

Page 177

Advertising
background image

PLCopenPlus Function Blocks for Motion Control 2013-04-13

169

6. If the Torque input is positive, and the Direction input equals
MC_Direction#negative_direction, then the Torque input is
negated. However, for compatibility with previous versions, the Direction
input is ignored if the Torque input is negative since the reverse direction
is implied.

7. When a soft position limit is exceeded, MC_TorqueControl will be
aborted and the axis will be switched into position mode. In this case, the
axis will decelerate according to ServoPack parameters Pn80D, Pn80E,
Pn80F and Pn827.

Torque Input

Direction Input

Axis Direction of Motion

Positive

Positive

Positive

Positive

Negative

Negative

Negative

Negative

Negative

Negative

Positive

Negative

Related Function Blocks

Y_DirectControl

: Control mode 3 on Y_DirectControl block available from

the Y_Motion firmware library allows the user to specify a commanded
torque every scan.

Error Description

ErrorID

Meaning

0

No Error

4369

The move could not be buffered because the axis motion
queue is full. 16 moves is the maximum which can be
buffered.

Advertising