Commissioning

Commissioning steps (overview)

Basic settings with GDC

6

l

117

EDBCSXP064 EN 8.0

6.4.1

Basic settings with GDC

)

Note!

ƒ

The settings are required for operation with a linear or continuous
positioning axis.

ƒ

Comply with the commissioning steps in the given order.

Setting

Brief description

Detailed

information

Preconditions

l

Mains is switched off. (Green LED is dark, red LED is
blinking)

l

Controller inhibit is active.

– Press the <F9> key in GDC.
– X6/SI1 orX6/SI2 must be open (LOW).
– Control bit Ctrl1.Rsp = 1

1.

Switch on low−voltage supply
(24 V DC).

2.

Connect PC/laptop (with
installed GDC parameter
setting program) to
controller.

Connection to X14 (system bus (CAN)) with PC system bus
adapter EMF2177IB.

^ 259

3.

Start GDC and select the
device to be set.

Select device:
Change to the online mode via the GDC toolbar with the
<F4> key and select "Searching for drives" using the <F2>
key.

ð The drive is identified and the parameter menu is opened.

GDC online
help

4.

Load Lenze setting.

l

Not required for initial commissioning of the axis module.

l

Only recommended if the Lenze setting is unclear.

^ 125

5.

Set communication
parameters according the
interface used.

Comm. parameters − CAN interface:

l

CAN node address (via DIP switch or C0350/C2450)

l

Baud rate (via DIP switch or C0351/C2451)

l

C0356 (CAN boot up/cycle time)

l

C1120 = 1 (sync connection via MotionBus (CAN))

l

C1121 (synchronisation cycle [in ms])

^ 266

^ 274

^ 278

Comm. parameters − AIF interface:
Please also read the documentation for the Lenze
communication module used!
AIF: Electrical shaft via EtherCAT with PLC as electrical shaft
master (EMF2192IB)

l

C1120 = 2 (synchronisation via terminal X6/DI1)

l

C1121 (synchronisation cycle [in ms])

l

The synchronisation cycle set under C1121 must be set
the same as the transmission cycle of the sync telegrams.

^ 224

6.

Set mains data.

Set the following codes in the GDC parameter menu under
Short setup

W Mains:

l

C0173 (voltage thresholds)

l

C0175 (function of the charge relay)
– For operation with the power supply module ECSxE set

C0175 = 3.

^ 126

7.

Enter motor data.

Lenze motors:
Use the GDC motor assistant.

^ 128

Motors from other manufacturers:
Set the codes in the GDC parameter menu under
Motor/feedback systems

W Motor setting.

^ 244

8.

Configure holding brake.

l

Not required if a holding brake is not available;

otherwise

l

Set C4023 (speed threshold) > 0 (e.g. 1 %) to apply the
holding brake.

^ 130