Commissioning

Quick stop (QSP)

6

l

243

EDBCSXP064 EN 8.0

6.28

Quick stop (QSP)

During the process, a quick stop (QSP) can be actuated via the control word Ctrl1 with
control bit Ctrl1.QSP = 1, i. e. the drive brakes to standstill along the QSP deceleration time
set (C0105) and a change to the "Stand−by" state is effected (status bit Stat2.QspIn = 1).

The quick stop deceleration time is set with C0105 in the GDC parameter menu under
Positioning/E−Shaft

W Positioning behaviour.

Code

Possible settings

IMPORTANT

No.

Designation

Lenze/
{Appl.}

Selection

C0042 DIS: QSP

Quick stop status (QSP)
Only display

^ 243

0

QSP not active

1

QSP active

C0105 QSP Tif

0.0

Deceleration time for quick stop
(QSP)

^ 243

0.000

{0.001 s}

999.999 Relating to speed variation n

max

(C0011) ...0 rev./min.