Technical data – Lenze ECSCPxxx User Manual

Page 35

Advertising
background image

Technical data

Current characteristics

Increased continuous current depending on the control factor

3

l

35

EDBCSXP064 EN 8.0

The following table shows the connections between mains voltage, DC−bus voltage and
motor voltage:

Mains voltage

[U

mains

]

DC−bus voltage

[U

DC

= U

mains

x 1.35]

Output voltage (motor voltage)

nominally achievable for 100 %

modulation

[U

mot

= 0.66 x U

DC

]

3 x 230 V AC

310 V DC

3 x 205 V AC

3 x 380 V AC

510 V DC

3 x 340 V AC

3 x 400 V AC

540 V DC

3 x 360 V AC

3 x 415 V AC

560 V DC

3 x 370 V AC

3 x 460 V AC

620 V DC

3 x 415 V AC

3 x 480 V AC

650 V DC

3 x 435 V AC

3 x 528 V AC

712 V DC

3 x 475 V AC

For steady−state operation in generator mode with increased DC−bus voltage or supply
from a closed−loop DC−voltage source, interpolate accordingly between the values given in
the table.

The increased rated currents are valid for the entire voltage range specified at switching
frequencies of 4 kHz and 8 kHz.

)

Note!

If in this connection a heatsink temperature of > 70 °C is reached, the drive
switches to a switching frequency of 4 kHz, independently of the selected
switching frequency.