Electrical installation

Power terminals

Connection to the DC bus (+U

G

, −U

G

)

5

l

55

EDBCSXP064 EN 8.0

Fuses

ƒ

Mains fuses are not included in the Lenze delivery program. Use standard fuses.

ƒ

When using ECSxE power supply modules which are fused on the supply side the
DC−bus supply need not be fused.

ƒ

When ECS axis modules are supplied by devices of the 82xx and 93xx series with a
continuous DC current > 40 A, install the following fuses between the supplying
device and the ECS devices:

Fuse

Support

Value [A]

Lenze type

Lenze type

50

EFSGR0500ANIN

EFH20007

ƒ

Observe the national and regional regulations (VDE, UL, EVU, ...).

J

Warnings!

ƒ

Use UL−approved cables, fuses and fuse holders only.

ƒ

UL fuse:
– Voltage 500 ... 600 V
– Tripping characteristic "H", "K5" or "CC"

Replacing defective fuses

{

Danger!

Hazardous electrical voltage
Components can carry hazardous voltages up to 3 minutes after power−off.
Possible consequences:

ƒ

Death or severe injuries when touching the device.

Protective measures:

ƒ

Replace fuses in the deenergised state only.
– Set controller inhibit (CINH) for all axis modules in DC−bus operation and

disconnect all power supply modules from the mains.