Monitoring functions

Configuring monitoring functions
Current load of controller (I x t monitoring: OC5, OC7)

9

l

306

EDBCSXP064 EN 8.0

9.3.9

Current load of controller (I x t monitoring: OC5, OC7)

Fault message

Monitoring function

System variable

Possible response

TRIP

Messag

e

Warnin

g

Off

015

OC5

I x t overload

MCTRL_bIxtOverload_b

·

· Default setting

üSetting possible

The I x t monitoring function monitors the current load of the axis module. The monitoring
function is set so that operation

ƒ

is permanently possible with a device output current = I

r

.

ƒ

is possible for

£ 30 s with a device output current £ 1.5 x I

r

.

The overload protection of the axis module can be set with thresholds:

ƒ

adjustable threshold (OC7) via C0123

ƒ

fixed threshold (OC5) = 100 %

After an overcurrent phase, you can calculate with a recovery phase of 120 s. For a more
precise consideration, see the overcurrent characteristic and the value 3 x

t

axis module

(

^ 307).

The response to exceeding the adjustable threshold can be defined under C0604.

Code

Possible settings

IMPORTANT

No.

Designation

Lenze/
{Appl.}

Selection

C0123 OC7 limit

90

Threshold for I x t warning (axis
module)

^ 300

0

{1 %}

100 C0064 > C0123

ð fault message

OC7 (C0604)

C0604 MONIT OC7

2

Fault response − monitoring of
Ixt device utilisation.
Ixt threshold can be set under
C0123.

^ 300

0

TRIP

2

Warning

3

Off