Monitoring functions

Configuring monitoring functions
Motor temperature sensor monitoring (Sd6)

9

l

318

EDBCSXP064 EN 8.0

9.3.15

Motor temperature sensor monitoring (Sd6)

Fault message

Monitoring function

System variable

Possible response

TRIP

Messag

e

Warnin

g

Off

086

Sd6

Motor temperature sensor
fault

MCTRL_bSensorFault_b

ь

ь

·

· Default setting

üSetting possible

This monitoring function checks whether the motor temperature sensor supplies values
within the measuring range of −50 ... +250 °C. If the values are outside this measuring
range, monitoring is activated.

The response is set via C0594.

Code

Possible settings

IMPORTANT

No.

Designation

Lenze/
{Appl.}

Selection

C0594 MONIT SD6

3

Fault response − monitoring
KTY sensor for the motor
temperature.
"SensorFault" (Sd6)

^ 318

0

TRIP

2

Warning

3

Off