Commissioning

Commissioning steps (overview)
Set reference

6

l

120

EDBCSXP064 EN 8.0

Setting sequence

Setting

Brief description

Detailed

information

Preconditions

l

The axis module is ready for operation (RDY).
– Check with C0183, C0168/1
– Green LED is blinking, red LED is off

l

Controller inhibit is active.

– Press the <F9> key in GDC.
– X6/SI1 orX6/SI2 must be open (LOW).
– Control bit Ctrl1.Rsp = 1
– The homing status "Reference known"

(HomePosAvailable) has to be reset (C4045/bit 13 = 0).

1.

Define the positioning
profile.

Set the following codes in the GDC parameter menu in
Positioning profiles

WProfile 01:

l

C3095/1 = 101 (positioning profile mode "Set reference")

l

C3011 (home position offset)

l

C3012 (reference measuring system offset)

^ 191

2.

Start positioning profile
(profile 01).

Set the following codes in the GDC parameter menu in Short
setup

W Operating mode:

l

C4010 = 3 (control interface C4040)

l

C4040/bit 4 = 1 (control bit Ctrl1.PNoSet_1, select
positioning profile)

l

C4040/bit 8 = 1 (control bit Ctrl1.ProfEnable, start
positioning profile)

^ 158

ð Changeover to the "Positioning" state

– C4045/bit 4 = 1 (status bit Stat1.PStatPos)
– C4045/Bit 10 = 1 (status bit Stat1.ProfileBusy)

ð Home position is known.

– C4045/Bit 13 = 1 (status bit Stat1.HomPosAvail)

^ 161

3.

Reset positioning profile
selection.

Settings:

l

C4040/bit 4 = 0

l

C4040/bit 8 = 0

ð Changeover to the "Stand−by" state

– C4045/Bit 0 = 1 (status bit Stat1.PStatStdBy)
– C4045/Bit 4 = 0 (status bit Stat1.PStatPos)

The settings for the reference setting are now completed.

Proceed as follows:

ƒ

Set Manual jog (inching mode) (

^ 121).