Commissioning

Setting of homing parameters

Setting homing modes

6

l

181

EDBCSXP064 EN 8.0

Settings

Mode 2
(Homing in positive direction)

Mode 3
(Homing in negative direction)

l

Set C0540 = 2.

l

Set C3010 = 2.

l

Set C0540 = 2.

l

Set C3010 = 3.

Variant
(positive hardware limit switch = reference switch)

Variant
(negative hardware limit switch = reference switch)

Additionally

l

connect the positive hardware limit switch parallel
to X6/DI2 and X6/DI4.

l

Set C0114/2 = 1. (X6/DI2 is LOW−level active.)

Additionally

l

Connect the negative hardware limit switch parallel
to X6/DI1 and X6/DI2.

l

Set C0114/2 = 1. (X6/DI2 is LOW−level active.)

)

Note!

ƒ

Single−turn absolute value encoder (SinCos encoder) and resolver do not
have a zero pulse. Here the zero position corresponds to the zero pulse.

ƒ

For multi−turn absolute value encoders only homing modes 8 ... 15 can be
used (C3010 = 8 ... 15).