Communication with MotionBus/system bus (CAN)

Parameter data transfer

12

l

427

EDBCSXP064 EN 8.0

12.3.4.3

Examples of the parameter data telegram

Reading parameters

The heatsink temperature C0061 ( 43 °C) is to be read from the controller with node
address 5 via the parameter data channel 1.

ƒ

Identifier calculation

Identifier from SDO1 to controller

Calculation

1536 + node address

1536 + 5 = 1541

ƒ

Command "Read Request" (request to read a parameter from the controller)

Command

Value [hex]

Read request

0x40

ƒ

Index calculation

Index

Calculation

24575 − code number

24575 − 61 = 24514 = 0x5FC2

ƒ

Subindex: 0

ƒ

Telegram to controller

Identifier

User data

Command

Index

LOW byte

Index

HIGH byte

Subindex

Data 1

Data 2

Data 3

Data 4

1541

0x40

0xC2

0x5F

0x00

0x00

0x00

0x00

0x00

ƒ

Telegram from controller

Identifier

User data

Command

Index

LOW byte

Index

HIGH byte

Subindex

Data 1

Data 2

Data 3

Data 4

1413

0x43

0xC2

0x5F

0x00

0xB0

0x8F

0x06

0x00

– Command:

"Read Response" (response to the read request) = 0x43

– Identifier:

SDO1 from controller (1408) + node address (5) = 1413

– Index of the read request:

0x5FC2

– Subindex:

0

– Data 1 ... 4:

0x00068FB0 = 430000

W 430000 : 10000 = 43 °C